Installation guide

12
Functions
Advantys
STB Distributed I/O
Solution 0
Open and Modular System
The table below sets out the main features of the basic and standard Advantys STB
ranges:
(1) See below.
(2) Requires standard PDM power distribution modules.
(3) Fuse protection only.
(4) Requires standard NIM network interface module.
(5) To support internal island parameters, simplifies replacement of faulty devices (FDR) and
copying of island parameters.
When a module of the Advantys STB island is unplugged under power, the behavior
of the other modules depends:
b on the type (basic/standard) of the NIM network interface module.
b on the parameter settings of standard type I/O modules:
v mandatory/optional module.
v configured fallback type, per channel.
(1) Fallback level regulated by the software Advantys STB SPU 1
ppp
on standard I/O modules
with a standard NIM.
Software STB SPU 1
ppp
is not connected on NIM basic modules.
(2) The fallback state is adjustable on standard output modules:
- Fallback to 0 for digital modules.
- Fallback to 1 for digital modules.
- Fallback to any value on analog outputs.
- Hold last value on digital and analog outputs.
Basic/standard Advantys STB functions
I/O modules NIM network interface
modules
PDM power
distribution modules
Advantys STB Basic Standard Basic Standard Basic Standard see page
Max. no. of I/O modules
12 32 8 to 11
Field wiring connectors
Keying pin
39
Cold swapping
12
Hot swapping (1) (3)
12
Separate power supply to sensors and actuators
(2) (2) 26
Integrated electronic output protection
(3)
Electronic protection of power supply provided by
Advantys STB for sensors
Power supply protected by removable integrated fuse
Status LEDs
Compatible with all types of network interface module
CANopen extension - Device integration
11
Local HMI compatibility (Magelis)
90
Default configuration
82
Design, installation and maintenance supported by Advantys
software (4)
83
Configurable I/O parameters (4)
83
Built-in reflex functions
86
Removable memory card (4) (5)
16
Advanced diagnostics (4)
84
Internal software update (firmware)
17
Available function Non-available function Not applicable
Hot swapping
Unplugging of module Type of network interface module
Basic NIM Standard NIM (1)
Basic input
All outputs fall back to 0 Other outputs remain operational
Standard input optional
All outputs fall back to 0 Other outputs remain operational (1)
Standard input mandatory
All outputs fall back to 0 Fallback of other outputs depending on
parameter setting (1)(2)
Basic output
All outputs fall back to 0 Other outputs remain operational
Standard output optional
All outputs fall back to 0 Other outputs remain operational (1)
Standard output mandatory
All outputs fall back to 0 Fallback of other outputs depending on
parameter setting (1)(2)
PDM power distribution module
Illegal Illegal
NIM network interface module
Illegal Illegal