Installation guide
11
Description (continued)
Advantys
™
STB Distributed I/O
Solution 0
Open and Modular System
The CANopen extension module STB XBE 2100 can be used to connect, at the end
of the segment, external CANopen devices such as:
v IP67 Advantys FTB I/O, in plastic or metal casing.
v Altivar
®
31/61r/71r variable speed drives.
v Festo
®
CPV-CO2 electropneumatic valves.
v Parker
®
P2M2HBVC11600 electropneumatic valves.
v Balluff
®
Micropulse BTL5r linear encoders (1).
The number of CANopen external devices depends on the standard network
interface module of the island:
CANopen, DeviceNet external devices (up to 7 ).
Ethernet TCP/IP Modbus
®
, Modbus Plus
™
, INTERBUS
®
, Profibus DP, Fipio
®
external
devices (up to 12).
The baud rate of the internal bus is set to 500 Kbps with the configuration software
Advantys STB SPU 1ppp. This speed applies to all the Advantys STB modules and
to the external devices.
Standard Advantys STB with CANopen devices
A standard network interface module supports up to 32 I/O modules and external
CANopen devices (excluding PDM power distribution modules, network interface
module, bus termination, auxiliary power supplies, EOS/BOS bus extension modules
and CANopen STB XBE 2100 extension module).
The island bus can support:
b Preferred modules (available later). This type of preferred module is installed
between two segments.
b Standard CANopen devices.
The island bus in the above example comprises:
1 STB Npp 2212: an NIM (Network Interface Module).
2 STB PDT 3100: c 24 V PDM (Power Distribution Module).
3 STB EHC 3020: 1-channel counter module.
4 STB EPI 1145: parallel interface module.
5 STB DDI 3420: digital input modules.
6 STB EPI 2145: module for TeSys
®
Model U starter-controllers.
7 TeSys
®
Model U or TeSys
®
Quickfit starter-controller.
8 STB XBE 1000: EOS bus extension module It is always installed in the farthest
right slot in the primary or extension segment, and is used to extend the island bus
to another segment.
9 STB XCA 100p: island bus extension cables.
10 Preferred module.
11 STB XBE 1200: BOS bus extension module placed at the beginning of the segment.
12 STB ACp: analog I/O modules.
13 STB XBE 2100: CANopen extension module (up to 12 devices per island).
14 IP67 I/O Advantys FTB.
15 Altivar
®
variable speed drive.
r Pending or in process at time of printing.
(1) To obtain the latest list of qualified equipment on the Advantys STB island extension, please
consult your Regional Sales Office or visit www.us.telemecanique.com.
To validate a new product, please consult your Regional Sales Office.
Standard Advantys STB: CANopen extension module - Device Integration
Standard Advantys STB: Application-specific modules, preferred module and
devices
1 32 985 6 10 11 13 1494 123 49
7
15
up to 15 m (16.4 yd)
32 I/O modules or external devices
CANopen devices
up to 12 m (13.1 yd)
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com