User`s guide
FactoryCast Configurator
122
890 USE 152 00 Version 2.0
Resynchronizing Your Namespace with Its Database, Continued
To
Resynchronize
Resynchronizing will alter the item(s) that differ from the database. The
Configuration Tool allows only one resynchronization per configuration session.
Follow the steps in the table below:
If You Don’t
Resynchronize
Until the files are resynchronized, you will not be able to add, delete, change the
attributes of, or edit symbols and write-enabled direct addresses in the namespace.
Step Action
1 Select Commands | Resyncronize PLC Database.
2 Select File | Save.
Result: The Resyncronize Function changes the configuration to correct any
discrepancies.