Installation guide
Planning and Designing RIO Cable System
50
890 USE 101 00 October 2006
Grounding and Surge Suppression
Overview Choose a low impedance earth ground for your cable system, preferably factory
ground. Use 10 gauge wire or larger to ground the cable system. Use a common
single-point ground for the cable system and for all equipment associated with the
system. A separate ground—e.g., a computer ground—may actually cause more
noise because the RIO nodes will not be connected to it.
Earth Ground A low impedance earth ground is necessary on RIO cable systems to assure safety
for maintenance personnel and RIO users. The earth ground also provides a path to
dissipate noise on the cable system. If the ground is poor or nonexistent, a
hazardous shock problem may exist, the cable system will be susceptible to noise,
and data transmission errors will occur. The cable system should be single-point
grounded within 20 ft of the RIO processor—the central ground point may be a tap,
a splitter, or a ground block.
Lightning
Protection for
RIO Cable
Systems
Surge suppressors are recommended when a cable system is installed outdoors or
in any environment where lightning protection is required. The surge suppressor
must be grounded to work properly. An 8 gauge or larger diameter green or bare
grounding wire is recommended. Depending on the site, installation of the
suppressor can possibly introduce ground loops resulting in communication errors.
Drop communication status can be monitored through the use of the STAT block
mentioned in The S908 Status Table section of the Monitoring Remote I/O System
Status chapter of Modicon Ladder Logic Block Library User Guide, 840 USE 101 00.
Note: All nodes connected to the cable system must be grounded. Under no
circumstances should ungrounded equipment be connected to the cable system.
See Modicon Quantum Automation Series Hardware Reference Guide, Appendix
D: Power and Grounding Guidelines, 840 USE 100 00.