Installation guide
Planning and Designing RIO Cable System
890 USE 101 00 October 2006 21
Redundant RIO
Cable Systems
If both the head processor and the drop adapters have two cable ports, then
redundant linear cables can be run. A redundant topology provides two parallel
paths to the same remote I/O drops. It allows you to increase the communications
integrity on an RIO network, allowing the network to operate even when one cable
system is damaged or malfunctioning.
Note: Quantums use drop #1 for local I/O. When upgrading from a 984A, B, or X
PLC to a Quantum Automation Series PLC, the first drop in the RIO network will
need to be changed to a drop number other than #1.
P/S PLC RIO I/O I/O I/O
RIO Drop #2
RIO Drop #3
Last RIO Drop
P/S RIO I/O I/O I/O
P/S RIO I/O I/O I/O
P/S RIO I/O I/O I/O
Trunk Cable A Trunk Cable B
Trunk Terminator
Trunk Terminator
Tap
Tap
Tap
Tap
Tap
Tap