PCMCIA (E984-
275/285 Only)
The E984-275/285 CPUs support PCMCIA release 2.1 type II socket. The CPU
provides routines for accessing the PCMCIA card. Drivers are included to support
additional memory via AMD compatible memory cards. The card may be used to
store your application or as dynamic storage for data. You may write and read your
applications to either FLASH or PCMCIA card. You may use the PCMCIA card for
data logging from the user program via the DLOG instruction. (See Program Storage
using FLASH RAM & PCMCIA (E984-258/265/275/285 Only), p. 44).
Transferring
MEEP
Applications to
PCMCIA Cards
Applications on earlier models (A984-1xx, E984-24x/251/255) using MEEP cards
can not be directly ported to the newer models (E984-275/285). This occurs
because the PCMCIA card replaces the MEEP card. In this case, go into the
Concept directory and run convert.exe. This converts your Modsoft application files
to Concept project files. Then select your PLC type. However, your I/O map is not
converted because the E984-258/265/275/285 PLCs I/O drivers are different than
the older models. Thus, reenter your I/O map and validate your analog scaling within
your application. The PCMCIA card works in a similar manner as the MEEP in earlier
models.
PLC Login
Password
Protection
(E984-258/265/
275/285 Only)
This feature allows you to prevent unauthorized writes to the PLC via Modbus
commands. The password must be at least 1 character and may be up to 16
characters long. Valid characters are: a ... z, A ... Z, 0 ... 9. Spaces are NOT allowed
and the password is case sensitive. The default is no password. The PLC MUST be
stopped before entering a password. Checking the box labeled PLC level password
protection enables this option. The password is entered in two steps. First you enter
your password into a Concept dialog box to gain access to the PLC. Second, from
the main Concept menu select Online, Online Control Panel, then Set PLC-
Password... The Change PLC-Password dialog box appears. Enter your password.
Then confirm with OK. To deactivate the password feature, enter the old password
and press OK. This prompts a confirm to remove.
The following figure shows the Change PLC Login Password screen.
Change PLC Password
Enter Old Password:
Enter New Password:
OK Cancel Help