This table shows the Parts List for Callouts for Above and Below.
Callout Vendor (or
equivalent)
Part Number Description Instruction
1 Modicon Shipped with
backplane
Plastic Cover Installation is Required.
2 Flat Braid Cable.25in
(6.3mm) or wider
3 Modicon 043509693 Grounding Bar All cable shields must
be grounded.
4Steward
(Outside the
United States
call Livingston,
Scotland at
(0044) 1-506-
414-200)
28 B2400-000 Ferrite Bead
1.37in(34.8mm) I.D.;
2.5in (63.5mm) O.D.;
.44in (11.2mm) Thick
For a BMOT-201
ONLY: All cables
(Motor, I/O, Encoder
and I/O cables) must
pass through this large
ferrite bead. Secure it
with a tie wrap or
equivalent.
5 Braided Shielded
Cable. 80% shield
coverage, #of
conductor and gauge
per user
requirements.