User guide
Getting Started
148
890 USE 108 00 August 2001
Start-Up
Procedure Using
Modsoft with
Your Compact
Stage 3
This stage of the procedure ends with forcing on a coil.
Step Action
1 Prior to downloading the program. Connect your W952/110XCA20xxx or
equivalent cable between COM1 of your PC to Modbus port on the PLC. (if you
have a A984 or E984-241/251 PLC).
2 Ensure the MEM/DEF toggle switch is set to DEF. (if you have an A984 or
E984-241/251 PLC).
3 Select Transfer (F5).
4 Select File to PLC.
5 Press ENTER, and select your programTest.
6 Press ENTER. This will download your program to the Compact PLC.
7 A message appears and asks you if you want to start the PLC, type Y.
8 Hit Escape to back out to Modsoft’s main menu.
9 Select On Line (F3).
10 Select Direct to PLC.
11 Select the default communication parameters.
12 A message appears and asks you if you want to create a new network, type Y.
13 Press ENTER.
14 Press the TAB key once, this places the cursor in the network.
15 Select Elements (F3).
16 Select Relays (F1).
17 Select the open contact symbol -| |- (F1).
18 Enter reference number 100001, and press ENTER.
19 Select Elements (F3).
20 Select Relays (F1).
21 Select the coil symbol -( )- (F5).
22 Enter reference number 1, and press ENTER.