Start-Up
Procedure Using
Modsoft with
Your Compact
Stage 2
This stage of the procedure includes the configuration steps.
Step Action
1 Start Modsoft from Offline (F2) selection on the Main Menu.
2 Select New Programs (F2) from the menu.
3 Enter file name Test.
4 Use default path.
5 Select Address (F6) from the menu.
6 Use default Modbus 1 communication parameters.
7 Select Config Menu (F5).
8 Select Overview Menu (F3).
9 Select PLC Type.
10 Select Compact.
11 Select E255.
12 Use default configuration settings.
13 Select I/O Map, (F4) this places you at rack 1, slot position 101... 105. Leave slot
103 blank because the P120-000 power supply resides in this slot.
14 Move cursor to slot 104.
15 Hit Shift?, this gives you a list of possible I/O modules.
16 Select DEP216.
17 Enter your input reference 10001.
18 Select DAP216.
19 Enter your output reference 1.
20 Hit Quit (F9).
21 Hit Escape to back out to Modsoft’s main menu.