Technical information
7373
Description.(continued).
TeSys Quickt components for motor starters (continued)
Elements for prewiring the control section
For prewiring the control section, the TeSys Quickt system provides the control
connection module 8 LAD9AP3 for connecting motor starters to the processing
unit (PLC) via the Modicon parallel interface module 9 STBEPI2145K without the
use of tools.
The LAD9AP3control connection module is mounted directly on the contactor
and the circuit breaker of each motor starter. It integrates the status and control
information of this motor starter.
A mechanical locking device 2 for the system on the head of the contactor ensures
faultless connection regardless of the conditions of use (vibration, shock, etc.). Four
versions are available: for direct or reversing start, with or without contactor coil
interface relay.
The lower part of the LAD9AP3 module has several external connectors,
including an RJ45 socket, for connection to the STBEPI2145K parallel interface
module via RJ45 cables 10 LU9R , which are available in different lengths.
The following information is available for each motor starter:
2 inputs: status of circuit breaker and status of contactor
1 output: contactor coil control
Connection to the STBEPI2145K parallel interface module:
A direct motor starter uses 1 RJ45 channel
A reversing motor starter uses 2 RJ45 channels
(1).Please.consult.the.“Motor.starter.solutions.Motor.control.and.protection.components”.
catalogue
Modicon STB distributed I/O
solution
TeSys Quickt for motor starter
components
9