Technical information

7373
Description.(continued).
TeSys Quickt components for motor starters (continued)
Elements for prewiring the control section
For prewiring the control section, the TeSys Quickt system provides the control
connection module 8 LAD9AP3 for connecting motor starters to the processing
unit (PLC) via the Modicon parallel interface module 9 STBEPI2145K without the
use of tools.
The LAD9AP3control connection module is mounted directly on the contactor
and the circuit breaker of each motor starter. It integrates the status and control
information of this motor starter.
A mechanical locking device 2 for the system on the head of the contactor ensures
faultless connection regardless of the conditions of use (vibration, shock, etc.). Four
versions are available: for direct or reversing start, with or without contactor coil
interface relay.
The lower part of the LAD9AP3 module has several external connectors,
including an RJ45 socket, for connection to the STBEPI2145K parallel interface
module via RJ45 cables 10 LU9R , which are available in different lengths.
The following information is available for each motor starter:
2 inputs: status of circuit breaker and status of contactor
1 output: contactor coil control
Connection to the STBEPI2145K parallel interface module:
A direct motor starter uses 1 RJ45 channel
A reversing motor starter uses 2 RJ45 channels
(1).Please.consult.the.“Motor.starter.solutions.Motor.control.and.protection.components”.
catalogue
Modicon STB distributed I/O
solution
TeSys Quickt for motor starter
components
9