Technical information
6969
Applications Parallel interface for TeSys U and TeSys
Quickt starter-controllers
Counting Applications HART multiplexer
Interface connections 4 RJ45 connectors (cables to be ordered
separately)
18-way spring-type removable connector
(supplied with the module)
Interface connections STBXTS2150, 18-way spring-type removable connector (supplied with the module)
Mounting base (supplied with the module) STBXBA3000, size 3 (28.1 mm) Mounting base (supplied with the module) STBXBA3000, size 3 (28.1 mm)
Swapping
Cold swap Yes Swapping
Cold swap –
Hot swap Yes, depending on NIM and conguration with Advantys STB conguration software Hot swap Yes
Power supply 24 V via STBPDT3100K/3105K module
(requires 21 V min.)
24 V via STBPDT3100K/3105K module Power supply 24 V
Operating voltage range 19.2…30 V
Consumption On 5 V logic bus 110 mA 100 mA Consumption On logic bus 400 mA
On 24 V sensor bus 100 mA max. –
On 24 V actuator bus 50 mA min. (with all 8 outputs at state 0)
80 mA by outputs at state 1 (220 mA max.
for 150 ms)
–
Inputs Number 12, 3 per RJ45 port (states of the TeSys U/
TeSys Quickt)
2 counter inputs (INA and INB) and 2 auxiliary
inputs (RST and EN)
Reverse polarity detection Yes
Voltage 24 V nominal
15…30 V at state 1
-3…+5 V at state 0
24 V nominal
15…30 V at state 1, -3…+5 V at state 0
40 kHz max.
Input logic (1) Default Positive Positive for all channels
Sensor power provided No
Congurable – Positive or negative for each channel
Outputs Number 8 (2 per RJ45 port) (forward and reverse
commands)
2 (OUT1 and OUT2)
Number of channels 4 HART channels
Nominal voltage 24 V (limits 21…30 V) 24 V (limits 19.2…30 V)
Output fallback states (1) Default All channels to 0 Set to state 0 for both output channels
Signal ltering for analog pass-through 1 passive lter of 25 Hz with a 3 dB attenuation point
Congurable Hold last value, set to state 0 or 1 for each channel
Output logic.(1) Default Positive for all channels
Channel to channel isolation 30 V minimum
Congurable Positive or negative for each channel
Operating modes Possible to connect:
- 4 TeSys U starter-controllers
- 4 TeSys Quickt direct motor starters
- 2 TeSys Quickt reversing motor starters
Frequency counting, event counting, period
measurement, one-off counting,
modulo (loop) counting, up/downcounting (1)
Data format Floating point
Protection against short-
circuits and overloads
On sensor bus 1 A fuse integrated in the module (2) and 5 A
fuse in the PDM module (3)
– Operating temperature, horizontal mounting (4) 0…60°C
On actuator bus 5 A fuse integrated in the module (2) and 5/10
A fuse in the PDM module (3)
–
On outputs Yes, per channel (internal electronic)
Operating temperature, horizontal mounting (4) -25...70°C (5)
Storage temperature -40…85°C
Module type Standard
STBEPI2145K STBEHC3020KC
Module type Standard
STBAHI8321KC
Basic Basic
Page
74 79
Page
80
(1).Conguration.with.Advantys.STBSPU1pppp.software.connected.on.a.standard.NIM.module
(2).Fuse.cannot.be.replaced.on-site
(3).Fuse.can.be.replaced.by.the.user
(4).Vertical.mounting:.apply.derating.of.8°C.to.the.operating.temperatures.for.horizontal.mounting
(5).For.extended.operating.temperatures.range,.the.power.consumption.can.be.only.calculated.using.Advantys.or.Unity.Pro.software
More technical information on www.schneider-electric.com