Technical information

6565
Modicon STB distributed I/O
solution
Analog I/O modules
Description
Description
Analog I/O modules comprise:
1 Two latches for locking the module on the base.
2 An LED display block indicating the various states of the module:
Basic I/O modules Standard I/O modules Indication
Green RDY LED Green RDY LED Module status (1)
Red ERR LED Module error (2)
3 A slot for a customizable label (on the module).
4 A colour-coded module identication stripe (see colour codes on page 4).
5 Two connectors for removable screw or spring-type terminals.
6 A mounting base specic to the module.
7 A slot for a customizable label (on the base).
The references of the analog I/O modules provide all the parts required for their
installation:
Appropriate mounting base for the module: STBXBA1000 (size 1, width 13.9 mm)
or STBXBA2000 (size 2, width 18.4 mm).
STBXTS1100 screw-type or STBXTS2100 spring-type 6-way removable
terminals.
To be ordered separately:
Earthing of the cable shielding is mandatory. The STBXSP3000 optional earthing
kit can also be used to secure cables in installations subject to severe vibration.
8 STBXSP3000 optional earthing kit, comprising 2 lateral supports, 1 metal bar
(length 1 m) and 1 earthing terminal.
9 STBXSP3010 terminals for 1.5…6 mm
2
cross-section cables or STBXSP3020
terminals for 5…11 mm
2
cross-section cables.
Optional mechanical keying pins:
Between I/O module and I/O base: STBXMP7700
Between wiring connectors and I/O module: STBXMP7800
These devices ensure that the I/O modules, bases and wiring connectors are
properly matched after dismantling or replacement.
Sheets of customization labels: STBXMP6700.
(1).RDY.LED.on:.module.OK.RDY.LED.off:.no.power.from.PDM.RDY.LED.ashing:.fault.
present
(2).ERR.LED.on:.internal.error.ERR.LED.off:.module.OK.ERR.LED.ashing:.module.error.
Please.consult.the.“System.Hardware.Components.Reference.Guide”.included.on.the.
STBSUS8800.CD-ROM.or.available.on.our.website.wwwschneider-electriccom
7
1
2
3
4
5
1
6
9
8