Technical information
61
More technical information on www.schneider-electric.com
61
Applications Analog input modules Analog input modules
Current Current Multirange
Number of channels 2 4 8 2
Range 4…20 mA 0...20 mA 4…20 mA (default)
0...20 mA
4…20 mA (default)
0...20 mA
HART protocol tolerant
4…20 mA (default)
0...20 mA
Thermocouples B, E, J, K, R, S and T
Temperature probe Pt 100, Pt 1000,
Ni 100, Ni 1000, Cu 10 ± 80 mV
Resolution 10 bits 12 bits 15 bits + sign
Isolation Channel-to-channel 30 V (when sensor voltage is separate from logic bus voltage) 200 V 30 V (when sensor voltage is
separate from logic bus voltage)
–
Response time 5 ms for both channels 8 ms for all 4 channels 80 ms for all 4 channels – –
Acquisition period – – 150... 360 ms (depending on range)
Acquisition or update time 10 ms for both channels 10 ms for all 4 channels 85 ms for all 4 channels 22 ms for all 8 channels 10 ms for both channels
Input low-pass lter Cut-off frequency 25 Hz 985 Hz 25 Hz
Internal power supply for 3-wire inputs Yes No Yes –
Connection (connectors supplied with modules) 2 x STBXTS1100 screw-type or STBXTS2100 spring-type 6-way connectors 2 x STBXTS1100 screw-type or STBXTS2100 spring-type 6-way connectors
Base (supplied with modules) STBXBA1000, size 1 (13.9 mm) STBXBA2000, size 2 (18.4 mm) STBXBA1000, size 1 (13.9 mm)
Power distribution
modules (PDM) (1)
Voltage 24 V 24 V
Reference STBPDT3100K/3105K STBPDT3100K/3105K
Protection Reverse polarity Yes, by time-lag fuse on the Power Distribution Module (PDM) Yes, by time-lag fuse on the Power Distribution Module (PDM)
Short-circuit and overload – – Yes, by time-lag fuse on the PDM
Electronic protection of
sensor power supply
No Yes No
Cut sensor wire detection No Yes (2) Yes (2) Yes (4…20 mA only) Yes (2)
Absolute accuracy at 25°C +/-0,75% of full scale +/-0,5% of full scale +/-0,4% of full scale (6)
Offset calibration constant (2) – 0 ... +8191
(representing 0 ... +5.12 mA)
– –
Maximum count (2) – 23 800 ... 32 760
(representing 14.88 ... 20.48 mA)
– –
Hot swapping supported Yes, with standard NIM only Yes, with standard NIM only Yes, with standard NIM only
Reex actions supported (2) No Yes, as inputs only Yes, for 2 inputs only (1 and 2) No Yes, as inputs only
Operating temperature, horizontal mounting (3) 0…60°C (4) -25…70°C (5) -25…70°C (5) 0…70°C (4)
Current consumption on 5 V c logic bus 30 mA 95 mA 90 mA 30 mA
Module type Standard
STBACI1230K STBACI0320K STBACI8320K STBACI1400K STBART0200K
Basic
STBACI1225K
Page 66 66 66
(1).One.Power.Distribution.Module.(PDM).is.required.per.voltage.group
(2).Requires.Advantys.STBSPU1ppp.software
(3).Vertical.mounting:.apply.derating.of.8°C.to.the.operating.temperatures.for.horizontal.mounting
(4).For.standard.operating.temperatures.range,.the.power.consumption.can.be.calculated.using.Advantys.or.Unity.Pro.software,.or.a.handwritten.sheet.available.at.
the.end.of.this.catalog.(see.page.114).or.an.Excel.worksheet.available.on.our.website,.wwwschneider-electriccom
(5).For.extended.operating.temperatures.range,.the.power.consumption.can.be.only.calculated.using.Advantys.or.Unity.Pro.software
(6).Please.refer.to.our.web.site.wwwschneider-electriccom