Technical information

5454
Functions.
STB digital output module operating modes
Output protection and reset following overload or short-circuit
Modicon STB digital output module Short-circuit and thermal
overload protection
Actuator power supply
protection
Reset Diagnostics
Basic modules, STBDDO3415K, 3605K, 3705pp Internal electronic Via PDM fuse On elimination
of the fault
Per group of
2 channels
Standard modules, STBDDO3200K, 3230K
Actuator powered by the module
Internal electronic Internal electronic Congurable (1) Per channel
Standard modules, STBDDO3200K, 3230K
Actuator powered externally
Internal electronic Via external fuse Congurable (1) Per channel
Standard modules, STBDDO3410K, 3600K Internal electronic Per group of
2 channels
Standard modules, STBDRC3210K, STBDRA3290K External fuse Congurable (1)
Standard modules, STBDAO8210K External fuse Via external fuse Congurable (1)
Standard modules, STBDAO5260K External fuse Congurable (1)
Behaviour of digital output modules upon internal communication fault on the island or between PLC and NIM
Modicon STB digital output module Output fallback
Basic modules, STBDDO3415K, 3605K, 3705pp
0 (open output)
Standard modules, STBDDO3200K, 3230K, 3410K, 3600K
STBDRC3210K, STBDRA3290K
STBDAO8210K, STBDAO5260K
Congurable (2)
Hot swapping and cold swapping of output modules
Swapping a module While energized: Hot swap Cold swap
Standard NIM Any type of NIM
Basic digital output module The other I/O modules remain operational (3) All I/O modules and power distribution modules
(PDM) can be removed from the island.
The removable connectors make it easier to do this.
Standard digital output module
not congured “mandatory”
The other I/O modules remain operational (3)
Standard digital output module
congured “mandatory”
Output fallback according to conguration (3)(4)
The island switches to pre-operational mode.
The inputs are no longer updated on the network/eldbus.
Power distribution module (PDM) Not permitted
(1).The.reset.is.user-congurable:.automatic.on.elimination.of.the.fault.(default.factory.conguration).or.intentional.by.the.PLC..
Each.module.can.be.congured.independently.This.operation.requires.the.Advantys.STBSPU1ppp.conguration.software.
The.tripping.data.is.transmitted.to.the.PLC.via.the.NIM.network.interface.module
(2).The.fallback.is.user-congurable:.to.0.(default.factory.conguration),.to.1,.or.to.“hold.last.value”.for.warm.standby.and.hot.standby.applications..
Each.output.channel.on.each.module.can.be.congured.separately.
This.operation.requires.the.Advantys.STBSPU1ppp.conguration.software.
(3).The.STBSPU1ppp.conguration.software.can.be.connected.via.a.standard.NIM.All.standard.I/O.modules.can.be.congured.Basic.modules.are.not.
congurable.(default.factory.settings.only)
(4).For.standard.digital.output.modules,.the.fallback.state.is.congurable:.
-.Fallback.to.level.0.
-.Fallback.to.level.1.
-.Fallback.to.a.predened.level.of.the.output.range.for.analog.modules.
-.Hold.last.value
Modicon STB distributed I/O
solution
Digital I/O modules