Technical information
5151
Applications Digital (discrete) output modules Digital (discrete) output modules
DC/AC (relay) AC (triac)
Nominal output voltage 24 V(relay contact)
115/230 V (relay contact)
115 V 115/230 V
Number of channels 2 NO/NC contact relays and common 2 contact relays NO + NC 2
Outputs Logic Default Positive Positive
User-congurable
(1)
Positive or negative, selection by channel Positive or negative, selection by channel
Internal power supply for
3-wire actuators
No Yes
Load current 2 A per contact 7 A per contact
2 A at 30°C
1 A at 60°C
Response time Off-to-on 5.25 ms 10 ms 0.5 cycles 10 ms
On-to-off 6.75 ms 10 ms 0.5 cycles 10.5 ms
Fallback modes Default Both channels de-energized Both channels to 0
User-congurable (1) Hold last value or each channel energized or de-energized Hold last value or each channel set to 0 or 1
Connection Two STBXTS1100 screw-type or STBXTS2110 spring-type 5-way connectors Two STBXTS1100 screw-type or STBXTS2110 spring-type 5-way connectors
Base STBXBA2000 STBXBA3000 STBXBA2000, size 2 (18.4 mm)
Power distribution modules
(PDM) (2)
Voltage 24 V (relay coil) – 115/230 V
Reference STBPDT3100/3105K – STBPDT2100/2105K
Isolation Channel-to-bus 1780 V for 1 minute 1780 V for 1 minute
Channel-to-channel 500 V for 1 minute 1780 V for 1 minute –
Protection Reverse polarity – Yes
Short circuit and overload Yes (3) (4) Yes (3)
Electronic protection of
actuator power supply
No No
Hot swapping supported Yes, with standard NIM and depending whether the module is mandatory. See page 55 Yes, with standard NIM and depending whether the module is mandatory. See page 55
Reex actions supported (1) Yes, 2 max. Yes, 2 max.
Operating temperature, horizontal mounting (5) -25…70°C (6)(7) 0…60°C (8)
Current consumption on 5 V c logic bus 55 mA 70 mA 45 mA
Module type Standard
STBDRC3210K STBDRA3290K STBDAO5260K STBDAO8210K
Basic
Page 57
57
(1).Requires.the.STBSPU1ppp.conguration.software.
(2).One.power.distribution.module.(PDM).is.required.per.voltage.type
(3).Built-in.time-lag.fuses.on.the.power.distribution.module.(PDM)
(4).25.A.time-lag.fuses.recommended.on.each.channel.(not.supplied)
(5).Vertical.mounting:.apply.derating.of.8°C.to.the.operating.temperatures.for.horizontal.mounting
(6).With.limiting.between.60°C.and.70°C:.
-.Only.one.channel.active.at.any.time,.to.be.ensured.by.the.application.Example:.control.of.both.directions.of.operation.of.a.motor.
-.Maximum.load:.2.A.for.STBDRC3210K,.4.A.for.STBDRA3290K.
-.Maximum.supply.voltage:.245.V.c
(7).For.extended.operating.temperatures.range,.the.power.consumption.can.be.only.calculated.using.Advantys.or.Unity.Pro.software
(8).For.standard.operating.temperatures.range,.the.power.consumption.can.be.calculated.using.Advantys.or.Unity.Pro.software,.or.a.handwritten.sheet.available.at.
the.end.of.this.catalog.(see.page.114).or.an.Excel.worksheet.available.on.our.website,.wwwschneider-electriccom
More technical information on www.schneider-electric.com