Technical information

4949
Applications Digital (discrete) input modules Digital (discrete) input modules
AC AC
Nominal input values Voltage 115 V 230 V
Frequence 50/60 Hz 50/60 Hz
Number of channels 2 2
Sensor type 2 or 3-wire + earth 2-wire 2 or 3-wire + earth
Inputs Logic Default Positive Positive
User-congurable
(1)
Positive or negative, selection by channel Positive or negative, selection by channel
Type (IEC/EN 61131-2) Type 1 Type 1
Internal power supply for
3-wire sensors
Yes No Yes
Connection Two STBXTS1110 screw-type or STBXTS2110 spring-type 5-way connectors Two STBXTS1110 screw-type or STBXTS2110 spring-type 5-way connectors
Base STBXBA2000, size 2 (18.4 mm) STBXBA2000, size 2 (18.4 mm)
Power distribution modules
(PDM) (2)
Voltage 115 V 230 V
Reference STBPDT2100/2105K STBPDT2100/2105K
Isolation Channel-to-bus 1780 V for 1 minute 1780 V for 1 minute
Channel-to-channel 1780 V, 1 minute
Protection Reverse polarity Yes Yes
Short circuit and overload Yes, 5 A time-lag fuse on the power distribution module (PDM) Yes, 5 A time-lag fuse on the power distribution module (PDM)
Electronic protection of
sensor power supply
Yes No Yes
Hot swapping supported Yes, with standard NIM only Yes, with standard NIM only
Reex actions supported (1) Yes, 2 max. Yes, 2 max.
Operating temperature, horizontal mounting.(3) 0…60°C (4) 0…60°C (4)
Current consumption on 5 V c logic bus 40 mA 45 mA 40 mA
Module type Standard
STBDAI5230K STBDAI5260K STBDAI7220K
Basic
Page 56
56
(1).Requires.the.STBSPU1ppp.conguration.software.
(2).One.PDM.power.distribution.module.is.required.per.voltage.type
(3).Vertical.mounting:.apply.derating.of.8°C.to.the.operating.temperatures.for.horizontal.mounting
(4).For.standard.operating.temperatures.range,.the.power.consumption.can.be.calculated.using.Advantys.or.Unity.Pro.software,.or.a.handwritten.sheet.available.at.
the.end.of.this.catalog.(see.page.114).or.an.Excel.worksheet.available.on.our.website,.wwwschneider-electriccom
More technical information on www.schneider-electric.com