Technical information
4646
Selection.guide.(continued)
Applications Digital (discrete) output modules Digital (discrete) output modules
DC (transistor) DC (transistor)
Nominal output voltage 24 V 24 V
Number of channels 2 4 6 16
Outputs Logic Default Positive on each channel Positive
User-congurable
(1)
Positive or negative, selection by channel – Positive or negative,
selection by channel
– Positive or negative, selection by
channel
–
Internal power supply for
3-wire actuators
Yes No No
Load current 0.5 A 2 A 0.25 A 0.5 A 0.25 A 0.5 A 0.5 max. per channel
Response time Off-to-on
620 ms for a 0.5 A load 520 ms 560 ms for a 0.25 A
load
560 ms for a 0.5 A load
550 ms at a resistive load of 250 mA 715 ms for a 0.5 A load
2 ms at 0.5 A load
On-to-off
575 ms for a 0.5 A load 720 ms 870 ms for a 0.25 A
load
870 ms for a 0.5 A load
900 ms at a resistive load of 250 mA 955 ms for a 0.5 A load
2 ms at 0.5 A load
Fallback modes Default All channels to 0 All channels to 0
User-congurable (1) Yes.(2) – Yes.(2) – Yes.(2) –
Fault recovery response Default Manual reset Manual reset
User-congurable (1) Yes.(3) – Yes.(3) – Yes.(3) –
Connection Two STBXTS1100 screw-type or STBXTS2100 spring-type 6-way connectors Two STBXTS1100 screw-type
or STBXTS2100 spring-type 6-way connectors
Two STBXTS1180 screw-type
or STBXTS2180 spring-type
18-way connectors
Modicon Telefast ABE7 connector and
cable (10)
Base STBXBA1000, size 1 (13.9 mm) STBXBA1000, size 1 (13.9 mm) STBXBA3000, size 3 (28.1 mm) STBXBA3000, size 3 (28.1 mm) (11)
Power distribution modules
(PDM) (4)
Voltage 24 V 24 V
Reference STBPDT3100/3105K STBPDT3100/3105K
Isolation Channel-to-bus 1500 V for 1 minute 1500 V for 1 minute
Channel-to-channel – 500 V for 1 minute – –
Protection Reverse polarity Yes Yes
Short circuit and overload Yes (5) (6) Yes (5) Yes (5)
Electronic protection of
actuator power supply
Yes Yes, with internal
power supply
No No No
Hot swapping supported Yes, with standard NIM and depending whether the module is mandatory. See page 55 Yes, with standard NIM and depending whether the module is mandatory. See page 55
Reex actions supported (1) Yes, 2 max. No Yes, 2 max. No Yes, 2 max. No
Operating temperature, horizontal mounting (7) -25…70°C.(8) -25…70°C.(8) 0…60°C.(9) -25…70°C.(8) 0…60°C.(9) -25…70°C.(8) -25…70°C.(8)
Current consumption on 5 V c logic bus 50 mA 45 mA 70 mA 90 mA 135 mA
Module type Standard
STBDDO3200K STBDDO3230K STBDDO3410K STBDDO3600K
Basic
STBDDO3415K STBDDO3605K STBDDO3705KS/KC STBDDO3705 (12)
Page 56 56
(1).Requires.the.STBSPU1ppp.conguration.software.
(2).Fallback.states:.hold.last.value,.set.to.predened.value.(0.or.1).on.each.channel.individually
(3).Manual.or.automatic.reset,.congurable.for.standard.output.modules.on.an.island.equipped.with.a.standard.NIM.module
(4).One.power.distribution.module.(PDM).is.required.per.voltage.type
(5).Built-in.time-lag.fuses.on.the.power.distribution.module.(PDM)
(6).If.an.external.power.supply.is.used:.25.A.time-lag.fuses.recommended.on.each.channel.(not.supplied)
(7).Vertical.mounting:.apply.derating.of.8°C.to.the.operating.temperatures.for.horizontal.mounting
(8).For.extended.operating.temperatures.range,.the.power.consumption.can.be.only.calculated.using.Advantys.or.Unity.Pro.software
(9).For.standard.operating.temperatures.range,.the.power.consumption.can.be.calculated.using.Advantys.or.Unity.Pro.software,.or.a.handwritten.sheet.available.
at.the.end.of.this.catalog.(see.page.114).or.an.Excel.worksheet.available.on.our.website,.wwwschneider-electriccom
(10).Modicon.Telefast.ABE7.connector.and.cable.to.be.ordered.separately.(see.page.102)
(11).Base.to.be.ordered.separately
(12).For.use.with.the.Modicon.Telefast.ABE7.pre-wired.system.(see.page.102)
Modicon STB distributed I/O
solution
Digital I/O modules
DC (transistor) outputs
More technical information on www.schneider-electric.com