Technical information
3030
Applications Modicon STB island bus expansion Modicon STB island bus expansion
EOS end of segment BOS beginning of segment Island bus expansion for standard
CANopen devices
Auxiliary power supply
Interface connectors Island bus Firewire connector (1) Firewire connector Screw or spring-type 5-way
removable connector
–
24 V external power
supply
Screw or spring-type 2-way removable connector – Screw or spring-type 2-way removable connector
Base STBXBA2400, size 2 (18.4 mm) STBXBA2300, size 2 (18.4 mm) STBXBA2000, size 2 (18.4 mm) STBXBA2100, size 2 (18.4 mm)
24 V c external
power supply
Type 24 V non-isolated (19.2…30 V) (2) – 24 V non-isolated (19.2…30 V) (2)
Function TeSys U power supply connected as preferred
module
Built-in 5 V logic power supply – Additional 5 V logic power supply (7)
Protection on
24 V c power supply
Voltage surge Yes Yes – Yes
Reverse polarity Yes Yes – Yes
Short-circuit, overload Yes, resettable internal fuse Yes – Yes, automatically resettable internal fuse
5 V c logic power supply Voltage – 5.25 V ± 0.21% – 5.25 V ± 0.21%
Max. current 1.2 A (3) – 1.2 A (3)
Consumption on the logic
bus
– 25 mA 100 mA –
Hot swapping No No
Operating temperature,.horizontal mounting -25…70°C (6) -25…70°C (4) -25…70°C (6)(8) -25…70°C (4)
Module type Standard
STBXBE1100K (5) STBXBE1300K (5) STBXBE2100K STBCPS2111K
Basic
Page 34
34
(1).Also.used.to.carry.the.24.V.c.power.supply.for.a.TeSys.U.starter-controller.connected.as.preferred.module
(2).Use.a.24.V.c.external.SELV.(Safety.Extra.Low.Voltage).power.supply
(3).900.mA.for.operating.temperatures.between.60.and.70°C.
(4).BOS.expansion.module.STBXBE1300K.and.auxiliary.power.supply.module.STBCPS2111K:
.....-.For.-250°C.range,.the.supply.voltage.range.is.20430.V.c
.....-.For.060°C.range,.the.supply.voltage.range.is.19230.V.c
.....-.For.6070°C.range,.the.supply.voltage.range.is.192265.V.c
(5).Replace.the.old.EOS-BOS.module.pairing.STBXBE1000K.-.STBXBE1200K.with.the.EOS-BOS.module.pairing.STBXBE1100K.-.STBXBE1300K
(6).When.using.the.segment.in.extended.temperature.range.(-2570°C),.the.power.consumption.can.be.only.calculated.using.Advantys.or.Unity.Pro.software
(7).Used.when.the.I/O.module.current.consumption.in.one.segment.exceeds.12.A.Installed.in.the.the.primary.segment.or.the.expansion.segments..
in.front.of.a.PDM.module
(8).Conforming.to.the.range.of.operating.temperatures.for.connected.CANopen.devices
Selection.guide Modicon STB distributed I/O
solution
Internal bus expansion,CANopen expansion,
auxiliary power supply module
More technical information on www.schneider-electric.com