Technical information

1919
Applications Data exchange between master PLC and Modicon STB island I/O modules Data exchange between master PLC and Modicon STB island I/O modules
Bus or network type Modbus Plus Fipio InterBus Probus DP DeviceNet
Bus or network Type Industrial LAN compliant with the Modbus
Plus standard
Open industrial eldbus compliant with the
FIP standard
InterBus industrial eld bus (generation 4) Probus DP V.0 industrial eld bus Network compliant with v.2.0 of the Open DeviceNet
Vendor Assoc. (ODVA)
Compliance with standards modbus.org EN 50170,Vol 3, Parts1-3, 2-3, 3-3, 5-3, 6-3
and 7-3
INTERBus Club DIN 19245, Parts 1 and 3 Open DeviceNet Vendors Association
Structure Physical interface Modbus Plus standard FIP standard Isolated RS 485 RS 485
Data rate 1 Mbps 1 Mbps 500 kbps 9.6 kbps…12 Mbps 125, 250 or 500 kbps
Medium Twisted pair Shielded twisted pair Shielded twisted pair Twisted pair
Conguration Number of devices
(1)
32 per segment
64 for all segments
32 per segment
128 max. for all segments
512 slaves max. with 254 bus terminal modules max 125 slaves 64 slaves
Maximum length 450 m per segment
1800 m with 3 repeaters
1000 m per segment 400 m per segment of the remote bus
12.8 km for the remote bus
50 m for the installation remote bus
1200 m (9.6 kbps)
4800 m with 3 repeaters
200 m (12 Mbps)
800 m with 3 repeaters
1200 m
Features of NIM module
(2)
Number of I/O modules per
Modicon STB island (1)
Standard NIM: 32 modules max. on 1 primary segment and 6 expansion segments maxi Standard NIM: 32 modules max. on 1 primary segment and 6 expansion segments max.
Input current 430 mA 430 mA
Supply voltage 24 V not isolated (19.2…30 V) (3) 24 V not isolated (19.2…30 V) (3)
Logic power supply (4) Output voltage: 5.25 V  ± 0.21 %
Nominal output current: 1.2 A (5)
Output voltage: 5.25 V  ± 0.21 %
Nominal output current: 1.2 A (5)
CANopen devices supported (6) 12 devices max. 7 devices max 12 devices max.
Connector type Bus or network port 9-way female SUB-D 9-way male SUB-D Input: 9-way male SUB-D
Output: 9-way female SUB-D
9-way female SUB-D 5-way male connector
RS 232 port (conguration,
dialogue with Magelis and
rrmware update)
HE 13, 8-way female HE 13, 8-way female
Services used - Global data
- Peer-to-peer
- Peer Cop
- Periodic I/O exchanges
- Point-to-Point message
- Use of standard proles (FRD/FSD/FED)
- Implicit exchange of process data
- Logical addressing
- Diagnostics
- Slave conguration
- Conguration control
- Read/write slave I/O data
- Diagnostics on Probus frames
- DeviceNet Object (Class ID3)
- Connection Object (Class ID5)
- Island Bus Object (Class ID101)
Operating temperature, horizontal mounting Standard NIM: -25…70°C (7)(8) Standard NIM: -25…70°C (7).(8)
Type of NIM module Standard
STBNMP2212 STBNFP2212 STBNIB2212 STBNDP2212 STBNDN2212
Basic
Page 22
22
(1).One.Modicon.STB.island.corresponds.to.1.device.on.the.bus.or.the.network
(2).See.table.of.functions.provided.by.the.basic.and.standard.Modicon.STB.ranges.(page.15)
(3).Use.a.24.V.c.external.SELV.(Safety.Extra.Low.Voltage).power.supply,.rated.at.minimum.700.mA.current.output
(4).Provides.logic.power.to.all.I/O.modules.on.the.primary.segment
(5).0575.A.for.operating.temperatures.between.60.and.70°C
(6).Connection.via.the.STBXBE2100K.CANopen.bus.expansion.module
(7).Standard.NIM.modules:.
....-.For.-250.°C.range,.the.supply.voltage.range.is.20430.V.c
...-.For..060.°C.range,.the.supply.voltage.range.is.19230.V.c
...-.For.6070.°C.range,.the.supply.voltage.range.is.192265.V.c
(8).When.using.the.segment.in.extended.temperature.range.(-2570°C),.the.power.consumption.can.be.only.calculated.using.Advantys.or.Unity.Pro.software
More technical information on www.schneider-electric.com