Technical information

1717
Applications Data exchange between master PLC and Modicon STB island I/O modules Data exchange between master PLC and Modicon STB island I/O modules
Bus or network type Ethernet Modbus TCP/IP, dual port Ethernet Modbus TCP/IP EtherNet/IP CANopen bus
Bus or network Type Industrial LAN Industrial LAN CAN eldbus
Topology Standard, daisy chain, daisy-chain loop Standard Standard
Compliance with standards IEEE 802.3 IEEE 802.3 CIA DS-301
Structure Physical interface 10/100 BASE-T, half/full duplex 10 BASE-T 10/100 BASE-T, half/full duplex ISO 1198
Data rate 10/100 Mbps 10 Mbps 10/100 Mbps 10 kbps…1 Mbps depending on bus length
Medium Double shielded twisted pair via Ethernet ConneXium cabling system Double shielded twisted pair via Ethernet ConneXium cabling system Double shielded twisted pair
Conguration Number of devices (1) 256 max. per segment, unlimited with switches 256 max. per segment, unlimited with switches 127 slaves
Maximum length 100 m according to 802.3 standard, > 100 m with ConneXium cabling system 100 m according to 802.3 standard, > 100 m with ConneXium cabling system From 30 m (1 Mbps) to 5000 m (10 kbps)
Features of NIM module
(2)
Number of I/O modules per
Modicon STB island (1)
Standard NIM: 32 modules max. on 1 primary segment and 6 expansion segments max. Standard NIM: 32 modules max. on 1 primary segment and 6 expansion
segments max.
Standard NIM: 32 modules max. on 1 primary segment and 6 expansion
segments max.
Supply voltage 24 V not isolated (19.2…30 V) (3) 24 V not isolated (19.2…30 V) (3)
Input current 550 mA 430 mA 430 mA
Logic power supply (4) Output voltage: 5.25 V  ± 0.21 %
Nominal output current: 1.2 A (5).
Output voltage: 5.25 V  ± 0.21 %
Nominal output current: 1.2 A (5)
CANopen devices supported (6) 12 devices max. 12 devices max. 7 devices max.
Interface connectors Bus or network port 2 x Female RJ45 (embedded switch) Female RJ45 Female RJ45 9-way male SUB-D
RS 232 port (conguration,
dialogue with Magelis and
rrmware update)
HE 13, 8-way female HE 13, 8-way female
Services used - Embedded Web (conguration, diagnostics
and access to variables )
- Modbus TCP/IP
- SNMP agent
- DHCP and BOOTP client services
- Embedded Web (conguration, diagnostics
and access to variables)
- Modbus TCP/IP
- SNMP agent
- DHCP and BOOTP client services
- Embedded Web (conguration, diagnostics and access to variables)
- SNMP agent
- DHCP and BOOTP client services
- Process Data Object (PDO)
- Service Data Object (SDO)
- Network management (NMT)
Operating temperature, horizontal mounting Standard NIM: -25…70°C (7)(8) Standard NIM: -25…70°C (7)(8)
Type of NIM module Standard
STBNIP2311 STBNIP2212 STBNIC2212 STBNCO2212
Basic
Page 22
22
(1).One.Modicon.STB.island.corresponds.to.1.device.on.the.bus.or.the.network
(2).See.table.of.functions.provided.by.the.basic.and.standard.Modicon.STB.ranges.(page.15)
(3).Use.a.24.V.c.external.SELV.(Safety.Extra.Low.Voltage).power.supply,.rated.at.minimum.700.mA.current.output
(4).Provides.logic.power.to.all.I/O.modules.on.the.primary.segment
(5).0575.A.for.operating.temperatures.between.60.and.70°C
(6).Connection.via.the.STBXBE2100K.CANopen.bus.expansion.module
(7).Standard.NIM.modules:.
....-.For.-250.°C.range,.the.supply.voltage.range.is.20430.V.c
...-.For..060.°C.range,.the.supply.voltage.range.is.19230.V.c
...-.For.6070.°C.range,.the.supply.voltage.range.is.192265.V.c
(8).When.using.the.segment.in.extended.temperature.range.(-2570°C),.the.power.consumption.can.be.only.calculated.using.Advantys.or.Unity.Pro.software
More technical information on www.schneider-electric.com