Technical information

1515
Functions.(continued)
Modicon STB distributed I/O
solution
Open and modular system
Hot swapping
When a module on the standard type Modicon STB island is unplugged under power,
the behaviour of the other modules depends on the parameter settings of standard
type I/O modules :
Mandatory or optional module
Congured fallback type per channel.
Swapping a module Behaviour of the other modules (1)
Basic input The other outputs remain operational
Standard input optional The other outputs remain operational (1)
Standard input mandatory Fallback of other outputs according to conguration (1)(2)
Basic output The other outputs remain operational
Standard output optional The other outputs remain operational (1)
Standard output mandatory Fallback of other outputs according to conguration (1)(2)
Power distribution module (PDM) Prohibited
NIM network interface Prohibited
Operating environment
Modicon STB devices comply with the following certications (3):
UL
CSA
C-Tick
GOST
CE
FM (class 1, division 2, groups A, B, C, D T4A @ 70°C).
ATEX 3G (II 3 G Ex nA IIC T4 Ta=0...60 °C) (4).
They benet from merchant navy certications issued by shipping classication
societies:
ABS (USA)
BY (France)
DNV (Norway)
GL (Germany)
LR (Great Britain)
RINA (Italy)
RMRS (IEC, pending)
They are designed for use in industrial environments of pollution class 2, in
applications of overvoltage category II (as dened in publication IEC 60664-1) and at
altitudes of up to 2000 m, without reduction in load.
Protection enhanced with a coating is provided on request, for use in harsh industrial
environments (see page 117).
(1).Fallback.level.set.by.the.Advantys.STBSPU1ppp.software.on.standard.I/O.modules.with.a.
standard.NIM..
The.STBSPU1ppp.software.cannot.be.connected.on.basic.NIM.modules
(2).The.fallback.state.is.adjustable.on.standard.output.modules:
.- Fallback.to.0.for.digital.modules
.- Fallback.to.1.for.digital.modules
.- Fallback.to.any.value.on.analog.outputs
.- Hold.last.value.on.digital.and.analog.outputs
(3).Certications.for.all.automation.products.(see.page.112)
(4).For.ATEX.zones.not.covered.by.this.specication,.Schneider.Electric.offers.a.solution.under.
the.CAPP.program.(Collaborative.Automation.Partner.Program).Please.consult.our.Customer.
Care.Centre
Note:.Limiting.supply.voltages.The.supply.voltages.for.NIM.modules,.STBXBE1300K,.
STBXBE1100K,.STBCPS2111K,.STBPDT3100K,.as.well.as.all.the.external.supply.voltages,.are.
limited.as.follows.for.the.ranges.of.operating.temperatures.below:
.- for.the.range.-250°C.,.the.supply.voltage.range.is.20430.V.c
.- for.the.range.060°C.,.the.supply.voltage.range.is.19230.V.c
.- for.the.range.6070°C.,.the.supply.voltage.range.is.192265.V.c.