Technical information

1212
Standard Modicon STB congurations (continued)
TeSys U starter-controller as preferred module
The island bus can support TeSys U starter-controllers as preferred modules
(installation between 2 island segments).
TeSys U starter-controllers must be equipped with a Modicon STB LULC15 serial
communication module.
The characteristics and advantages of this solution are:
Advanced process control (integrated in the Advantys software), such as reading
current data, detailed diagnostics, remote reset, etc.
Conguration with Advantys software
Hot swapping not possible (see page 15).
2
1
5
5
8 10
11
43
9
6
6
7
TeSys.U.as.preferred.module.on.a.standard.Modicon.STB.
The island bus in the above example comprises:
1 Modicon STB primary island segment.
2 STBN21: A standard NIM network interface module.
3 Removable screw connector for connection of an external 24 V power supply,
required for the TeSys U LULC15 communication module.
4 STBXBE1100K: End of segment, used to connect the preferred TeSys U
modules.
5 Angled cable with an island bus extension cable connector at each end, providing
the bus signals and the internal power supply (LU9RCD).
6 Modicon STB LULC15 serial communication modules
7 TeSys U starter-controller (LUB) with an advanced control unit (LUCB/C/D).
8 TeSys U starter-controller (LUB) with a multifunction control unit (LUCM).
9 Angled cable with an island bus extension cable connector at each end, providing
the bus signals and the internal power supply (LU9RDD).
10 STBXBE1300K: Beginning of segment.
11 STBXMP1100: A bus termination plate (1).
(1).Supplied.with.the.NIM.network.interface.module
Congurations.(continued)
Modicon STB distributed I/O
solution
Open and modular system
15 m max. with 32 I/O modules or
external devices