Technical information

107107
Phaseo regulated switch mode power supplies ABL8RPS/RPM/WPS (1)
Input
voltage
Secondary Reset Conforming
to IEC/EN
61000-3-2
Reference Weight
kg
Output
voltage
Nominal
power
Nominal
current
Single-phase (N-L1) or 2-phase (L1-L2) connection
100…120 V a -
200...500 V a
- 15%,+ 10%
50/60 Hz
24...28.8 V 72 W 3 A Auto/man Yes ABL8RPS24030 0.300
120 W 5 A Auto/man Yes ABL8RPS24050 0.700
240 W 10 A Auto/man Yes ABL8RPS24100 1.000
100…120 V/ -
200...240 V
- 15%,+ 10%
50/60 Hz
24...28.8 V 480 W 20 A Auto/man Yes ABL8RPM24200 1.600
3-phase connection (L1-L2-L3)
380…500 V a
± 10%
50/60 Hz
24...28.8 V 480 W 20 A Auto/man Yes ABL8WPS24200 1.600
960 W 40 A Auto/man Yes ABL8WPS24400 2.700
Phaseo regulated switch mode power supplies ABL4RSM/WSR (1)
Input
voltage
Secondary Reset Reference Weight
kg
Output
voltage
Nominal
power
Nominal
current
Single-phase (N-L1) connection.(2)
100…230 V a
- 10%, + 15%
23…27.4 V 85 W 3.5 A Automatic ABL4RSM24035 0.500
120 W 5 A Automatic ABL4RSM24050 0.500
120 V a
- 25%, + 10%
and
230 V a
- 20%, + 15%
23…27.4 V 240 W 10 A Automatic ABL4RSM24100 0.800
24…27.8 V 480 W 20 A Automatic ABL4RSM24200
(3)
1.300
3-phase (L1-L2-L3) connection
400…500 V a
- 15%, + 10%
24…27.8 V 480 W 20 A Automatic ABL4WSR24200 1.300
720 W 30 A Automatic ABL4WSR24300 1.300
960 W 40 A Automatic ABL4WSR24400 1.300
Function modules for continuity of service (4)
Function Use Description Reference Weight
kg
Continuity after
a power outage
Holding time 100 ms at 40 A and
2 s at 1 A
Buffer module ABL8BUF24400 1.200
Holding time 9 min at 40 A...2 hrs
at 1 A (depending on use
with a battery check module-
battery unit and load).(5)
Battery check module,
20 A output current
ABL8BBU24200 0.500
3.2 Ah battery module (6) ABL8BBU24400 0.700
7 Ah battery module (6) ABL8BPK24A03 3.500
7 Ah battery module (6) ABL8BPK24A07 6.500
12 Ah battery module (6) ABL8BPK24A12 12.000
Continuity
after a failure
Paralleling and redundancy of the
power supply to ensure uninterrupted
operation of the application excluding
supply failures and application
overloads
Redundancy module ABL8RED24400 0.700
Discriminating
downstream
protection
Electronic protection (1...10 A overload
or short-circuit) of 4 output terminals
from a Phaseo ABL8RPS/RPM/WPS
or ABL4RSM/WSR power supply
Protection module with
2-pole breaking (7)(8)
ABL8PRP24100 0.270
Separate and spare parts
Description Use Composition Unit reference Weight
kg
Fuse assemblies ABL8PRP24100 discriminating
protection module
4 x 5 A, 4 x 7.5 A and
4 x 10 A
ABL8FUS01
ABL8BKP24Abattery 4 x 20 A and 6 x 30 A ABL8FUS02
Clip-on marker
labels
All products except ABL8PRP24100 Order in multiples of 100 LAD90 0.030
ABL8PRP24100 discriminating
protection module
Order in multiples of 22 ASI20MACC5
DIN rail
mounting kit
ABL8BPK24A03 battery module ABL1A02
EEPROM
memory
Backup and duplication of
ABL8BBU2400 battery check module
parameters
SR2MEM02 0.010
(1).Certain.offers.can.not.be.marketed.in.certain.countries,.please.consult.our.Customer.Care.Center
(2).2-phase.connection.possible.on.certain.American.line.supplies.
(3).Power.supply.reference.ABL4RSM24200.has.an.integrated.redundancy.diode
(4).For.use.with.Phaseo.power.supplies.ABL8RPS/RPM/WPS.or.ABL4RSM/WSR
(5).Compatibility.table.for.battery.check.module-battery.unit.with.holding.time.depending.on.the.load..
......More.technical.information.on.wwwschneider-electriccom
(6).Supplied.with.20.or.30.A.fuse.depending.on.the.model
(7).Supplied.with.four.15.A.fuses
(8).Local.reset.via.pushbutton.or.automatic.reset.on.elimination.of.the.fault
References
Modicon STB distributed I/O
solution 0
Phaseo regulated switch mode power supplies
ABL8RPS24050
ABL8RPM24200
ABL8WPS24200
ABL4RSM24100
ABL4WSR24200
ABL4RSM24050
ABL8BUF24400
PF106349PF513585PF513586PF100286BPF100287BPF100851APF513587