Run LED Status The following table lists each available state of the Run LED indicator and provides
diagnostic information for that state in both the 140 NOE 771x1 module and the 140
NWM 100 module.
Indicator State Status for 140NOE771x1 Status for 140NWM100
On (steady) Normal operation: The NOE module
is ready for network communication.
Normal operation: The NOE
module is ready for network
communication.
Number of flashes in sequence
1 Not used Not used
2 Not used Not used
3 No Link: the network cable is not
connected or is defective
No Link: the network cable is not
connected or is defective
4 Duplicate IP address: The module
will be set to its default IP address.
Duplicate IP address: The module
will stay off-line.
5 No IP address: The module is
attempting to obtain an IP address
from a BOOTP server. Module is set
to its default IP address.
No IP address: The module is
attempting to obtain an IP address
from a BOOTP server.
6 Invalid IP configuration. (Likely
cause: Default gateway is not on the
same subnet mask.) Module is set
to its default IP address.
Using default IP address
7 No valid executive NOE present No valid executive NOE present
8 Not used Not used
9 - Flash file system inoperative.