Get Local Statistics
Description A get local statistics operation reads the data from the local node in one cycle and
does not require a master transaction path.To program an MBP_MSTR block to get
local statistics, use function code 3 (see Operational Function Codes, p. 151).
Network
implementation
A get local statistics operation can be performed on Modbus Plus and TCP/IP
Ethernet networks (see TCP/IP Ethernet Network Statistics, p. 174).
Control Block
Usage for
Modbus Plus
Control Block
Usage for TCP/IP
Ethernet
Register Meaning
CONTROL[1] 3 = read local statistics
CONTROL[2] indicates the error status.
CONTROL[3] Number of addresses to be read from local statistics (0...53)
CONTROL[4] First address from which the statistics table must be read (Reg1=0)
CONTROL[5] Routing register 1 is used to specify the address (routing path address 1 of
5) of the node during a network transfer.
The last byte in the routing path that is not 0 is the destination mode.
Register Meaning
CONTROL[1] 3 = read local statistics
CONTROL[2] indicates the error status.
CONTROL[3] Number of addresses to be read from local statistics (0...37)
CONTROL[4] First address from which the statistics table must be read (Reg1=0)
CONTROL[5] Routing register
Most significant byte: Network adapter module slot
CONTROL[6]
...
CONTROL[9]
Not used