Transferring Data Using Communication Blocks
162
33002479 06 07/2008
7303 Read/Write QSE module status (200 route address out of range)
7309 Attempt to write to a write protected register when a status write is carried
out (200 route)
731D Invalid route found by the Quantum translator.
Valid routes:
z dest_drop, 0xFF
z 200, dest_drop, 0xFF
z 100+drop, dest_drop, 0xFF
z All other routing values produce an error
734B One of the following errors occurred:
z No CTE (configuration extension table) has been configured
z No CTE table entry has been made for the QSE model slot number
z No valid drop has been specified
z The QSE module has not been reset after the creation of the CTE.
Note: After writing and configuring the CTE and downloading to the QSE
module, the QSE module must be reset for the modifications to become
effective.
z When using an MSTR instruction no valid slot or drop has been specified