User manual

Transferring Data Using Communication Blocks
33002479 06 07/2008 161
SY/MAX-Specific Error Codes
SY/MAX-Specific
Error Codes
When utilizing SY/MAX Ethernet, three additional types of errors may appear in the
CONTROL[1] register of the control block ().
The error codes have the following meaning:
z 71xx Error: Errors found by the SY/MAX remote device
z 72xx Error: Errors found by the server
z 73xx Error: Errors found by the Quantum translator
SY/MAX-Specific
Hexadecimal
Error Codes
SY/MAX-specific hexadecimal error codes:
Hex. Error
Code
Description
7101 Invalid opcode found by the SY/MAX remote device
7103 Invalid address found by the SY/MAX remote device
7109 Attempt to write to a write protected register found by the SY/MAX remote
device
F710 Receiver overflow found by the SY/MAX remote device
7110 Invalid length found by the SY/MAX remote device
7111 Remote device not active, no connection (occurs when retry attempts and
time-out have been used up), found by the SY/MAX remote device
7113 Invalid parameter in a read operation found by the SY/MAX remote device
711D Invalid route found by the SY/MAX remote device
7149 Invalid parameter in a write operation found by the SY/MAX remote device
714B Invalid drop number found by the SY/MAX remote device
7101 Invalid opcode found by the SY/MAX server
7203 Invalid address found by the SY/MAX server
7209 Attempt to write to a write protected register found by the SY/MAX server
F720 Receiver overflow found by the SY/MAX server
7210 Invalid length found by the SY/MAX server
7211 Remote device not active, no connection (occurs when retry attempts and
time-out have been used up), found by the SY/MAX server
7213 Invalid parameter in a read operation found by the SY/MAX server
721D Invalid route found by the SY/MAX server
7249 Invalid parameter in a write operation found by the SY/MAX server
724B Invalid drop number found by the SY/MAX server
7301 Invalid opcode in an MSTR block request from the Quantum translator