User manual
Transferring Data Using Communication Blocks
33002479 06 07/2008 151
Operational Function Codes
Valid MBP_MSTR
Function Codes
Using the MBP_MSTR block, one of 14 available network communication operations
can be triggered via the network. Each operation has a function code assigned to it.
The availability of specific operations depends on the type of network you are using.
where:
z X indicates Yes
z - indicates No
Function
Code
Operation Modbus
Plus
TCP/IP
Ethernet
SY/MAX
Ethernet
1 Write data X X X
2 Read data X X X
3 Get local statistics X X -
4 Clear local statistics X X -
5 Write global data, Peer Cop X - -
6 Read global data, Peer Cop X - -
7 Get remote statistics X X -
8 Clear remote statistics (see Clear
Remote Statistics, p. 173)
XX -
9 Peer Cop health status X - -
10 Reset optional module - X X
11 Read CTE (Config extension) - X X
12 Write CTE (Config extension) - X X
13 Send email (see Send Email, p. 183)X
23 Read/write data (see Read/Write Data,
p. 185)
X