User guide

Maintenance
58
840 USE 115 00 Version 1.0
The default is 0.
This is the minimum command. It will displa
y
the error lo
g
of the Ethernet web
embedded server module in slot 1 of the controller at Modbus Plus address 49.
.
This will displa
y
the error lo
g
of the Ethernet web embedded server module in slot 4
of the controller at Modbus Plus address 49.50. It will displa
y
debu
g
information,
use software interrupt 5d and use Modbus Plus adapter number 1. The output will
be redirected to a file named TRACE.OUT.
If
y
ou have entered a viable command, ERRLOG will respond:
Path DM. x. x. x. x. x was opened
where
x
is the Modbus Plus address of the Quantum controller.
Next, it will list the number and date of the Quantum Ethernet web embedded
server firmware version.
Then, for each entr
y
in the error lo
g
, ERRLOG will displa
y
the followin
g
information:
Error lo
g
entr
y
number.
File name:Line:error code:
The ten re
g
isters of the microprocessor in hexadecimal
(
EAX, EDX, ECX,
EBX, EBP, ESI, EDI, ESP, EFLAGS, EIP
)
.
For hardware exceptions, the file name and line number will be replaced b
y
the
hardware exception vector number in decimal.
If
y
ou have re
q
uested debu
g
messa
g
es, ERRLOG will also displa
y
the Modbus
messa
g
es and responses between the controller and the PC.
ERRLOG 49 1
Example
ERRLOG 49.50 4 /d /s5d /n1 > TRACE.OUT
Example