Technical information
3/29
Modicon M580 automation
platform
Modbus Plus Proxy module
References
TCSEGDB23F24FA
Embedded Web server
Web server functions
The Modbus Plus Proxy module includes an embedded Web server that can be used
to perform diagnostics and congure the module connection. All data is presented in
the form of standard Web pages in HTML format. To access a Web page, you need
Internet Explorer (version 6.0 or later) and Java (version 1.5 or later).
Embedded Web server functions
1 - Setup: The Setup pages allow you to dene the parameters for several different
module services, including security, IP, SNMP, Global Data, Peer Cop and Ethernet
ports.
2 - Diagnostics: These network diagnostic pages contain Ethernet, TCP, and SNMP
statistics, as well as a log of the diagnostics performed.
Complementary characteristics
The following characteristics complement those introduced in the communication
selection guide on page 3/5:
b External power supply voltage: 19.2...31.2 V c
b Consumption: 300 mA max.
b Dissipated power: 6.2 W
b Conformity with standards: UL 508, CSA 22.2 No. 142 (cUL), EMI EN 55011,
EN 61131-2, C-Tick
References
System and network requirements
Unity Pro XL programming software (version 3.x or later) (1)
Internet Explorer (version 6.0 or later)
Java (version 1.5 or later)
Microsoft Windows XP or Vista
Modicon M340 processors:
b BMXP342020 (Modbus and Ethernet version)
b BMXP3420302 (CANopen and Ethernet version)
b BMXP3420302CL (CANopen and Ethernet version) (2)
Modicon M580 processors:
b BMEP581020
b BMEP582020
b BMEP582040
b BMEP583020
b BMEP583040
b BMEP584020
b BMEP584040
Ethernet Modicon M340 communication modules:
b BMXNOE0100
b BMXNOE0110
b BMXNOC0401
Modicon M580:
b BMXNOC0402 (3)
Modicon Modbus Plus Proxy module
Description Type Reference Weight
kg
Modbus Plus Proxy module
for Modicon M340 and M580
PLCs
supplied with 2 front-mounted
power supply connectors
(2 positions)
Standard TCSEGDB23F24FA –
Conformal coating TCSEGDB23F24FK –
(1) Unity V8.0 or later with M580
(2) Memory card to be ordered separately for the BMXP3420302CL processor (see our website
www.schneider-electric.com).
(3) The BMXNOC0402 communication module will be replaced by the BMENOC03p1 modules
during the 2nd quarter of 2014..