Technical information
3/23
Modicon M580 automation
platform
Embedded web pages
Presentation (continued)
Diagnostic web pages (continued)
Redundancy page
This page displays values from the RSTP conguration in Unity Pro.
Parameters Description
Service Status This is the status (Enabled or Disabled) of the RSTP bridge on the
corresponding CPU
Last Topology
Change
These values represent the date and time that the last topology change
was received for the corresponding Bridge ID
Redundancy Status Green The designated Ethernet port is learning or formatting
information
Yellow The designated Ethernet port is discarding information
Gray RSTP is disabled for the designated Ethernet port
Router Bridge
Statistics
Bridge ID This unique bridge identier is the concatenation of the
bridge RSTP priority and the MAC address
Bridge Priority In Unity Pro, congure the RSTP operating state of the
Bridge ID
Alarm Viewer page
The Alarm Viewer page reports detected errors in the application. Information about
alarm objects can be read, ltered, and sorted on this page. The type of information
displayed by the Alarm Viewer is adjusted in the Filter Alarms box.
Field Description
Type This column describes the alarm type
Status STOP You need to acknowledge the alarm
ACK An alarm has been acknowledged
OK An alarm does not require acknowledgment
Message This column contains the text of the alarm message
Occurance This column contains the date and time that the alarm occurred
Acknowledged This column reports the acknowledged status of the alarm
Zone This column contains the area or geographical zone from which the alarm
comes (0: common area)
Alarm Viewer
Redundancy
2