Technical information

2
1
3
4
5
6
7
8
9
10
2
1
3
4
5
6
7
8
9
10
2
1
3
4
5
6
7
8
9
10
2
1
3
4
5
6
7
8
9
10
2/2 2/2
Overview
Modicon M580 automation
platform
I/O architectures
Modicon M580 type of architecture
Note: These architectures can be combined with each other
Architectures with local racks (main rack and expansion racks) Architecture with local racks (main rack and expansion racks) Architecture with racks in remote drops
Hardwired Distributed peripherals over eldbuses Distributed peripherals and I/O over Ethernet Remote over Ethernet
Compact topology with devices hardwired
on local I/O
Compact topology with devices distributed
over eldbuses
Distributed devices and I/O topology over Ethernet Remote I/O + Remote functions (including eldbus master)
Architecture A Architecture B Architecture C Architecture D
Expanded rack (with X-bus rack expansion module) Main local rack with up to 7 local expansion racks on X-bus (Modicon Premium or Modicon X80
racks)
Main local rack with up to 7 local expansion racks on X-bus (Modicon Premium
or Modicon X80 racks)
Main local rack with up to 7 local expansion racks on X-bus (Modicon Premium or
Modicon X80 racks), RIO drop with up to 1 remote expanded rack on X-bus (only
Modicon X80 racks)
Backplane compatibility BMEXBPpp00 Ethernet +
X-bus racks
Compatible for main racks (local or remote) Compatible for main racks (local or remote)
Mandatory for expansion racks (main or remote)
Compatible with any rack if Modicon X80 I/O Ethernet modules are not used in the racks, such as: weighing, HART and BMECRA31210 modules
BMXXBPpp00 X-bus racks
PV02 (or later)
Mandatory for expansion racks (main or remote)
Compatible with any rack if Modicon X80 I/O Ethernet modules are not used in the racks, such
as: weighing, HART and BMECRA31210 modules
Compatible CPU types All CPUs are compatible (1) All CPUs are compatible (1) BMEP58pp40 CPUs are required to manage RIO
CPU Ethernet ports SERVICE port One SERVICE port for HMI, Unity, control network, variable speed drive, etc. One SERVICE port for HMI, Unity, control network, variable speed drive, etc.
Dual port Dual ports are not used Dual ports are used for distributed equipment (DIO scanner) Dual ports are used for remote equipment (RIO scanner), BMECRA31210
Ethernet drop adapter is mandatory in RIO drop (2).
RIO drops A maximum of 16 RIO drops can be supported in an M580 network
Communication AS-Interface and serial link
modules
Yes Yes Yes, in a local rack or in a RIO drop
BMXNOR0200H RTU
module
Yes Yes Yes, only in a local rack
Ethernet modules Yes Ye s Yes, only in a local rack
Expert functions PTO (Pulse Train Output)
modules
Yes Yes Yes, only in a local rack
Other expert modules:
counting, SSI encoder, etc.
Yes Yes Yes, in a local rack or in a RIO drop
Time stamping 1 ms max. BMXERT1604T
module integrated in the ERT
module
Yes Yes Yes, in a local rack or in a RIO drop
10 ms with BMECRA31210
combined with discrete I/O
modules in the RIO drop
Yes, only in the RIO drop, system mode with OFS (2)
Pages
(1) BMEP58pp40 CPUs are not mandatory for architectures A, B and C.
(2) BMXCRA31210 modules are also compatible.
X-bus
HART
Ethernet
Ethernet
AS-I
Modbus
X-bus
2/2 2/3