Modicon M580 platform for Unity Pro software offer BMEP5810 model BMEP5820 models BMEP5830 models BMEP5840 models
Racks Maximum number of local racks 4
8
Remote I/O drop of 2 racks
8 16 16
I/O Maximum number of discrete I/O
channels (1)
1,024 2,048 3,072 4,096
Maximum number of analog I/O
channels (1)
256 512 768 1,024
Maximum number of Ethernet DIO
devices
64 128
64 128 64 128 64
In-rack application-
specic channels
Maximum number of application-
specic channels
24 32 64
Counter (1) BMXEHC0200
2-channel (60 kHz) or BMXEHC0800 8-channel (10 kHz) modules BMXEHC0200 2-channel (60 kHz) or BMXEHC0800 8-channel (10 kHz) modules
Motion control (1) BMXMSP0200 2-channel PTO (Pulse Train Output) module for servo drives BMXMSP0200 2-channel PTO (Pulse Train Output) modules for servo drives
Serial link (process or RTU) (1) BMXNOM0200 2-channel module or BMXNOR0200H module with 1 RTU serial channel BMXNOM0200 2-channel module or BMXNOR0200H module with 1 RTU serial channel
HART(1) BMEAHI0812 8-channel HART analog input (4–20 mA) module or BMEAHO0412 4-channel
HART analog output (4–20 mA) module
BMEAHI0812 8-channel HART analog input (4–20 mA) or BMEAHO0412 4-channel HART analog output (4–20 mA) module
SSI encoder (1) BMXEAE0300 3-channel module (SSI) BMXEAE0300 3-channel module (SSI)
Time stamping (1) BMXERT1604T 16-channel discrete input (with 1 ms resolution) module BMXERT1604T 16-channel discrete output (with 1 ms resolution) module
Process control, programmable
loops
Process control EFB library Process control EFB library
Integrated
communication ports
Ethernet Service port (RJ45)
1 port for DIO devices, Unity, CNM, HMI, SCADA, diagnosis & external tools 1 port for DIO devices, Unity, CNM, HMI, SCADA, diagnosis & external tools
-
Ethernet Device Network dual ports
(RJ45)
2 ports support DIO mode to connect devices using DIO
scanner
2 ports support both RIO and
DIO mode to connect Modicon
X80 drops using deterministic
RIO scanner and devices
using DIO scanner
2 ports support DIO mode to connect
devices using DIO scanner
2 ports support both RIO and DIO
mode to connect Modicon X80 drops
using deterministic RIO scanner and
devices using DIO scanner
2 ports support DIO mode to connect
devices using DIO scanner
2 ports support both RIO and DIO
mode to connect Modicon X80 drops
using deterministic RIO scanner and
devices using DIO scanner
USB port 1 programming port (PC terminal) 1 programming port (PC terminal)
Communication
modules
(1)
Ethernet network Maximum number 2 3 4
Type of module BMXNOC0402 (2) network modules with 1 EtherNet/IP channel or Modbus TCP
communication protocol
BMXNOC0402 (2) network modules with 1 EtherNet/IP channel or Modbus TCP communication protocol
AS-Interface Maximum number 8 8
Type of module BMXEIA0100 master module BMXEIA0100 master module
Internal memory
capacity
Program (MB) 4 8 12 16
Data (KB)
384 768 1,024 2,048
Data storage (GB) 4 4
Application structure Master task 2 processing modes (cyclic, periodic) 2 processing modes (cyclic, periodic)
Fast task 1 processing mode (periodic) 1 processing mode (periodic)
Auxiliary tasks (AUX 0, AUX 1) 1 processing mode (periodic) 1 processing mode (periodic)
Event tasks I/O event 64 128
Timer event 16 32
Total I/O and Timer
event
64 128
No. of K instructions
executed per ms
100% Boolean (Kinstr/ms) 10 20 40
65% Boolean + 35% xed arithmetic
(Kinstr/ms)
7.5 15 30
Rack power supply 24 V c isolated, 24…48 V c isolated, or 100…240 V a power supply module 24 V c isolated, 24…48 V c isolated, or 100…240 V a power supply module
Modicon M580 processor
BMEP581020 BMEP582020
BMEP582040 BMEP583020 BMEP583040 BMEP584020 BMEP584040
(1) The maximum values for the number of I/O, application-specic channels, and the number of networks are not cumulative (they are limited by the maximum
number of slots in the conguration, 1 rack: 11, 2 racks: 23, 3 racks: 35 and 4 racks: 47.)
(2) The BMXNOC0402 communication module will be replaced by the BMENOC03p1 modules during the 2nd quarter of 2014.