Technical information

6/2
Standards and certications
The Modicon M580 automation platform has been developed to comply with the
principal national and international standards concerning electronic equipment for
industrial automation systems.
b Requirements specic to programmable controllers: functional characteristics,
immunity, resistance, safety, etc.: IEC/EN 61131-2, UL and CSA standards for
industry (UL 508, CSA E61131-2).
b Requirements specic to power utility automation systems: IEC/EN 61850-3.
b Merchant navy requirements of the major international organizations: unied in
IACS (International Association of Classication Societies).
b Compliance with European Directives for e marking:
b Low Voltage: 2006/95/EC
b Electromagnetic Compatibility: 2004/108/EC
b Ex areas:
v For USA and Canada: Hazardous location class I, division 2, groups A,B,C and D
v For other countries: e ATEX (directive 94/9/EC) or IECEx in dened atmosphere
Zone 2 (gas) and/or Zone 22 (dust).
v Up-to-date information on which certications have been obtained is available on
our website.
Protective treatment of the Modicon M580 automation
platform
The Modicon M580 platform meets the requirements of “TC” treatment (Treatment
for all Climates).
For installations in industrial production workshops or environments corresponding
to “TH” treatment (treatment for hot and humid environments), Modicon M580 must
be embedded in enclosures with minimum IP 54 protection.
The Modicon M580 automation platform offers protection to IP 20 level and
protection against pins (enclosed equipment) (1). They can therefore be installed
without an enclosure in reserved-access areas which do not exceed pollution level
2 (control room with no dust-producing machine or activity). Pollution level 2 does
not take account of more severe environmental conditions: air pollution by dust,
smoke, corrosive or radioactive particles, vapors or salts, attack by fungi, insects,
etc.
(1) In cases where a position is not occupied by a module, a BMXXEM010 protective cover must
be installed.
(e): tests required by European directives (e) and based on IEC/EN 61131-2 standards.
Characteristics
Service conditions and recommendations relating to the environment
Standards and
certications
Modicon M580 automation
platform
Standards, certications and environment
conditions
Modicon M580 automation platform Modicon M580 harsh automation platform
Temperature Operation °C 0...+ 60 - 25...+ 70
Storage °C - 40...+ 85 - 40...+ 85
Relative humidity
(without condensation)
Cyclical humidity % + 5 ... + 95 up to 55°C + 5 ... + 95 up to 55°C
Continuous humidity % + 5 ... + 93 up to 55°C + 5 ... + 93 up to 60°C
Altitude Operation m 0…2000 (full specication: temperature and isolation)
2000 ... 5000 (temperature derating: 1°C/400 m, isolation lost: 150 V c/1000 m)
Supply voltage Modicon X80 I/O power supply modules
BMXCPS2010 BMXCPS3020
BMXCPS3020H
BMXCPS3540T BMXCPS2000 BMXCPS3500
BMXCPS3500H
Nominal voltage V 24 c 24...48 c 125 c 100...240 a 100...240 a
Limit voltages V 18...31.2 c 18...62.4 c 100…150 c 85...264 a 85...264 a
Nominal frequencies Hz 50/60 50/60
Limit frequencies Hz 47/63 47/63
2
1
3
4
5
6
7
8
9
10
2
1
3
4
5
6
7
8
9
10