Product data

21
Architectures (continued)
Modicon
Quantum
Ethernet I/O
automation platform
ConneXium
managed switches
Example topologies
ConneXium
managed switches (continued)
Predened conguration les (continued)
Example topology with predened conguration les C5, C1 and C3 (1)
A common use of this preconguration is for interfacing a copper link with a ber optic link on the primary ring or
interfacing a ber optic link with a copper link. This type of architecture makes it possible to have Ethernet DIO or
Ethernet RIO drops some distance away from the PLC.
The switch preconguration also enables Ethernet RIO and/or several Ethernet DIO device clouds to be
connected to a secondary ring.
1
C5
C1
C5
C3
3
1
1
2
2
2
2
2
2
2
2
2
8
8
8
8
8
8
1
7
7
7
7
7
7
4
55
6
9
9
9
9
9
9
Ethernet link, ber optic medium
Ethernet link, copper medium
1110
(2)
Primary ring, copper/ber optic medium1
Ethernet RIO secondary ring, copper medium only2
Ethernet head adaptor 140CRP31200 installed in the Quantum rack3
ConneXium switch TCSESM083F23F1 with predened conguration le C1 4 (3)
ConneXium switch TCSESM063F2CU1/CS1 with predened conguration le C5 5 (3)
ConneXium switch TCSESM063F2CU1/CS1 with predened conguration le C3 6 (3)
Ethernet drop adaptor 140CRA31200 installed in each Ethernet RIO drop 7 (4)
Connection to Ethernet DIO device cloud, copper medium only8
Ethernet DIO device cloud 9 (5)
Ethernet communication module 140NOE77110 pp (2)
Ethernet Interlink cable TCS ECN 3M3M 1S4/1S4U (1 m) 11 (2)
(1) Non-exhaustive example. For additional specications, see our website www.schneider-electric.com.
(2) The Ethernet communication module 10 and Ethernet Interlink cable 11 are only required if there are Ethernet DIO devices in
the architecture.
(3) Also see page 18 (C1) or page 19 (C3 and C5).
(4) Each Ethernet RIO drop can comprise a primary and a secondary rack.
(5) Requires the Ethernet communication module 10 and Ethernet Interlink cable 11.