Hardware reference guide
CableFast Cabling
802
35013379 02 October 2007
Note: These are the maximum load current capacities of the 140CFA04000 and
CFG01600 terminal blocks:
1. When using the 140CFA04000 terminal block, the indicated module outputs are
limited to 0.5 A per point, 150 Vac maximum and 0.5 A per point, 150 Vdc
maximum.
2. When using the 140CFG01600 terminal block and either the 140XTS012xx or
140XTS102XX high power cables, the indicated module output ratings are 2 A
per point, 150 Vac maximum, and 2 A per point, 150 Vdc maximum.
3. The 140CFA04000 block does not incorporate an isometric barrier and is not
recommended for use with the 140ATI03000 TC module. Without such a barrier,
temperature readings may vary up to 2 degrees from one end of the block to the
other. If the application can tolerate this temperature error, the block (and
module remote CJC) may be used.
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com