Hardware reference guide

Pwr. & Grnding. Guide
792
35013379 02 October 2007
Table of
combination
This table shows the different possible combinations of Quantum power supplies.
Compatibility
Issues of DIO
z While it is possible to use a standalone or a summable power supply with a DIO
drop (as long as the DIO input is left unpowered), it is not possible to use a
redundant supply with the DIO drop.
z The added power supply must not be included in the system I/O map.
z The added power supply need not be of the same type as the DIO adapter. AC
powered supplies may be used with DC type adapters and vice-versa.
z DIO module current load with an added power supply is typically 200 mA.
Combination with
Power supplies A
l
o
n
e
1 piece 1 piece 1 piece 2 pieces
140 CPS 111 00
140 CPS 210 00
140 CPS 511 00
140 CPS 114 10
140 CPS 114 20
140 CPS 214 00
140 CPS 414 00
140 CPS 124 00
140 CPS 124 20
140 CPS 224 00
140 CPS 424 00
140 CPS 524 00
140 CPS 124 00
140 CPS 124 20
140 CPS 224 00
140 CPS 424 00
140 CPS 524 00
Standalone 140 CPS 111 00 X -- - ---- ----- - ----
140 CPS 211 00 X -- - ---- ----- - ----
140 CPS 511 00 X -- - ---- ----- - ----
Summable 140 CPS 114 10 X -- - XX-- ----- - ----
140 CPS 114 20 X -- - XX-- ----- - ----
140 CPS 214 00 X -- - --X- ----- - ----
140 CPS 414 00 X -- - ---X ----- - ----
Redundant 140 CPS 124 00 X -- - ---- X---- X----
140 CPS 124 20 X -- - ---- -XXX- - XXX-
140 CPS 224 00 X -- - ---- -XX-- - XX--
140 CPS 424 00 X -- - ---- -X-X- - X-X-
140 CPS 524 00 X -- - ---- ----X - ---X
Caption:
X : possible,
- : impossible.
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com