Hardware reference guide
Pwr. & Grnding. Guide
35013379 02 October 2007 779
Detailed AC
Powered System
The following figure shows the details for the AC powered system for CE
compliance.
The following table shows the list of parts for the AC Powed System figure.
AC Powered System for CE Compliance
Detailed Installation Illustration
AC LINE
(BROWN)
AC NEUT
(BLUE)
GND
G
RN/YEL)
EARTH
G
ROUND
PANEL
GROUND
SHIELD
12 3
4
BROWN
BLUE
CASE TAB
GREEN/YELLOW*
(TO GROUND SCREW ON
QUANTUM BACKPLANE)
Line Filter
BLUE
BROWN
BACKPLANE
GND SCREWS
Quantum Backplane
140 XBP XXX 00
GND
LEAD
Shield
GND Lead
*Note: Only one ground wire per backplane is required.
In redundant and summable systems, this lead is not
connected for the additional line filter/power supply.
Quantum Power Supply
Wire to the power supply as follows:
Line (Brown wire)
Neutral (Blue wire)
GND (Green/Yellow wire)
1346
5
Callout Vendor (or
equivalent)
Part Number Description Instruction
1 Offlex Series
100cy
35005 Line Cord Terminate the shield at panel
ground; the filter end of the
shield is not terminated.
2 Steward 28 B 0686-200 Ferrite Bead Install next to the filter and
secure with tie wraps at both
ends of the ferrite bead.
Fair Rite 2643665702
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com