NOTE: Each group: 3 A, 0 ... 60° C. Per module: 6 A, 0 ... 60° C
Inductance Internal diode protected, no limit on
inductance
Output Response (OFF - ON, ON - OFF) 1.0 ms, resistive
Switching Frequency 50 Hz maximum
Output Protection (internal) Group varistor and individual point over current
sense
Isolation
Field to Bus 2500 Vac for 1 minute
Group-to-Group 1200 Vac for 1 minute
Fault Detection Over current (see note below)
Bus Current Required
6 points ON 375 mA
12 points ON 650 mA
Power Dissipation 1.0 W + 0.77 W x number of points ON
External Power None
Fusing
Internal 4 A (Part # 043511382 or equivalent) See below for
the location of the fuses.
External Not required for this module.
Specifications
DDO88500 Output Point Operating Curve