140DAO84210 Quantum I/O AC Output 100 ... 230 Vac 4x4 Module
Overview The AC Output 100 ... 230 Vac 4x4 module switches 100 ... 230 Vac powered loads.
Specifications The following table shows the specifications for the 100 ... 230 VAC OUT module.
Specifications
Number of Output Points 16 in four 4 point groups
LEDs Active
F
1 ... 16 (Green) - Indicates point status
1 - 4, 5 - 8, 9 - 12, 13 - 16 (Red) - Indicated group has a
blown fuse or no field power
Required Addressing 1 word out
Voltage (rms)
Working 85 ... 253 Vac
Absolute Maximum 300 Vac for 10 s
400 Vac for 1 cycle
Frequency 47 ... 63 Hz
ON State Drop / Point 1.5 Vac
Minimum Load Current (rms) 5 mA
Maximum Load Current (rms)
Each Point * 4 A continuous, 85 ... 132 Vac rms,
3 A continuous, 170 ... 253 Vac rms
Each Group 4 A continuous
Per Module* 16 A continuous (See the derating chart)
Off State Leakage / Point (max) 2.5 mA @ 230 Vac
2.0 mA @ 115 Vac