Hardware reference guide

I/O Modules
634
35013379 02 October 2007
Module Zoom
Selections
(Outputs)
Push <Enter> to display and select the output type and the timeout state for the
module. Timeout state is assumed when sytem control of the module is stopped.
12-Point Output
Module
The 12-point output module is:
z 140DDO88500
I/O Map Register
Assignment
(Fault Inputs)
The 140DDO88500 can be configured as either 16 contiguous 1x references or as
one 3x register.
The following figure shows the inputs configuration.
Module Zoom
Selections
(Inputs)
Push <Enter> to display and select the input type. This selection appears if the
module is I/O mapped to a 3x register. The following figure shows the input type.
I/O Map Register
Assignment
(Outputs)
The 140DDO88500 can be configured as one output (4x) register in the following
format. The following figure shows the register format for outputs.
BIN
BCD
Output Type:
1234567 10 11 1289
Note: Do not use the BCD selection, as it will incorrectly display fault conditions.
BIN
BCD
input Type:
1234567 10 11 1289
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com