Hardware reference guide
I/O Modules
35013379 02 October 2007 623
Minimum
Version Levels
The following table shows the minimum version levels required.Modules marked
SV/PV/RL rather than V0X.0X0 exceed the minimum version levels in this table.
Version Label The following figure shows the version label.
Products Minimum Version Level (see
label illustration
User Action Required
CPUs and NOMs < V02.20 Executive upgrade to ≥ V02.10
≥ V02.20 None
RIOs < V02.00 Module upgrade
≥ V02.00 and < V02.20 Executive upgrade to ≥ V01.10
> V02.20 None
DIOs < V02.10 Module upgrade
≥ V02.10 None
Modsoft < V02.40 Upgrade to V02.40
≥ V02.40 None
ProWORX NxT >=V02.00
Concept >=V02.00 None
Software compatibility
When using a DIO drop and the CPU and the NOM executive software is not per
the compatibility chart, channels 17 ... 24 of this module will be seen as zeroes in
the controller when configured as discretes.
Failure to follow these instructions can result in injury or equipment damage.
CAUTION
Note: The version label is found on the top front of the module.