Hardware reference guide
Intrinsically Safe Modules
35013379 02 October 2007 471
The following is a CSA certified wiring diagram for this module.
Output 1 (+) Output 1 (-)
N/C N/C
Output 2 (+) Output 2 (-)
N/C N/C
Output 3 (+) Output 3 (-)
N/C N/C
Output 4 (+) Output 4 (-)
N/C N/C
N/C N/C
N/C N/C
N/C N/C
Output 5 (+) Output 5 (-)
N/C N/C
Output 6 (+) Output 6 (-)
N/C N/C
Output 7 (+) Output 7 (-)
N/C N/C
Output 8 (+) Output 8 (-)
N/C N/C
N/C N/C
I.S. Module
DIO 330 00
Blue Terminal Strip
Chassis
Ground
HAZARDOUS LOCATION
CLASS 1, DIVISION 1
GROUP A, B, C, D
(See Notes 1 & 2)
I.S. Field
Device
NON-HAZARDOUS LOCATION
Note 1. Only shielded cables
should be used for connections.
Shields should be left open at
the field end and connected to
chassis ground at the ground
Note 2. All negative output
terminals - Output 1 (-) thru
Output B (-) are internally
Note 3. Pins marked “N/C” (Not
Connected) are not electronically
I.S. +24 Vdc @ NO LOAD
screws on the backpalne.
connected to I.S. ground
connected to the module.
Note 4. Only Quantum
140 XBP oX oo backplanes
should be used for mounting
this module.
Notes related to
CSA certification
for this module.
Note 1. Entity parameters per
channel: V
oc
= 27.9 V
I
sc
= 119 mA
C
a
= 84 nf
L
a
= 1.0 mH
Note 2. Maximum non-
hazardous area voltage must
not exceed 250 V.
Note 3. Install in accordance
with Canadian Electrical Code,
Part I, for installation in Canada.
Note 4. Install in accordance
with the NEC (ANSI/NFPA 70)
and ANSI/ISA RP 12.6 for
installation in the United States.
Note 5. To maintain intrinsic
safety, shield for each cable
must be grounded and must
extend as close to the terminals
as possible.
Note 6. Intrinsically safe (I.S.)
cables of one module must be
routed separately from I.S.
cables of another module.
Note 7. I.S. devices when
connected to I.S. terminals must
satisfy the following conditions:
V
oc
< Vmax
I
sc
< Imax
C
a
> C
i +
C
cable
L
a
> L
i +
L
cable
Note 8. This module is certified
as a component for mounting in
a suitable enclosure where the
suitability of the final
combination is subject to
acceptance by CSA or an
inspection authority having the
jurisdiction.
31001366 Rev 00 140 DIO 330 00 Wiring Diagram