Hardware reference guide
Intrinsically Safe Modules
466
35013379 02 October 2007
The following is a FM certified wiring diagram for this module.
Input 1 (+) Input 1 (-)
N/C N/C
Input 2 (+) Input 2 (-)
N/C N/C
Input 3 (+)
Input 3 (-)
N/C N/C
Input 4 (+) Input 4 (-)
N/C N/C
N/C N/C
N/C N/C
N/C N/C
Input 5 (+) Input 5 (-)
N/C N/C
Input 6 (+) Input 6 (-)
N/C N/C
Input 7 (+) Input 7 (-)
N/C N/C
Input 8 (+) Input 8 (-)
N/C N/C
I.S. Module
DII 330 00
Blue Terminal Strip
Chassis
Ground
HAZARDOUS LOCATION
CLASS I DIV I GROUP A, B, C, D
CLASS II DIV I GROUP E, F, G
I.S. Field
Device
Note 1: Only shielded cables should be used for connections. Shields shoul
d
Note 3: Only 140 XBP 0xx 00 backplanes should be used for mounting
this module.
I.S. +8 Vdc
Note 4: The Entity Concept allows interconnection of intrinsically safe
apparatus with associated apparatus not specifically examined in
combination as a system when the approved values of Voc and
Isc for the associated apparatus are less than or equal to Vmax and
CLASS III DIV I
be left open at the field end and connected to chassis ground at the
Module end.
Note 2: Pins marked N/C are not electronically connected to the Module.
Imax for the intrinsically safe apparatus and the approved values of
Ca and La for the associated apparatus must be equal to or are
greater than Ci and Li for the intrinsically Safe apparatus plus all
cable parameters.
Ca ≥ Ci + Ccable; La ≥ Li + Lcable; Voc ≤ Vmax; Isc ≤ Imax
Note 5: Simple Apparatus is defined as a device which will neither generate
nor store more than 1.2V, 0.1A, 20uJ, or 25 mW. For examples
switches, Thermocouples, LEDs and RTDs, Etc.
Note 6: Wiring methods must be in accordance with National Electrical
Code NFPA 70, Article 504 and ANSI/ISA RP12.6, “Wiring Practices
for Hazardous (classified) Locations Instrumentation
Part I: Intrinsic Safety”.
Note 7: Control room equipment connected to associated apparatus
should not use or generate more than 250Vrms.
Note 8: All modules must be installed in an enclosure that meets the
requirements of ANSI/ISA S82.01
Note 9: No revision to this drawing without prior FMRC Approval.
N/C N/C
140 DII 330 00 Wiring Diagram
31001365 Rev 01
HAZARDOUS LOCATION,
Class I, Div 2 Group A, B, C, D
Note 10. For Schneider Electric internal use only. For control sheet, refer
to 19-100986 Rev 1.
Note 11. For Division 2 installation, the apparatus shall be installed in
requirements of the ultimate application, including access only by the use
of a tool and provision for Division 2 wiring methods.
compliance with the enclosure, mounting, spacing, and segregation
This IS field device should meet Note 5 or should be FM approved or connection with IS RTD/TC IN Modules with
Concept Parameters listed below. The entity parameters are per Channel.
Voc = 9.6 VDC
Isc = 80 mA/Module
Ca = 450 nf/Ch
La = 0.694 mH/Ch
Po = 192 mW/Module
Notes Related to FM Certification