Hardware reference guide

Intrinsically Safe Modules
426
35013379 02 October 2007
I/O Map Status
Byte
The I/O map status byte is used by the 140AII33000 module as follows.
Modsoft Module
Zoom Selections
Use Modsoft’s Zoom feature to select the module input type and then configure the
eight channels appropriate to the input type selected.
12345678
MSB
Channel 1 out of range or short circuit
Channel 2 out of range or short circuit
Channel 3 out of range or short circuit
Channel 4 out of range or short circuit
Channel 5 out of range or short circuit
Channel 6 out of range or short circuit
Channel 7 out of range or short circuit
Channel 8 out of range or short circuit
LSB
RTD/Resistance
TC/mV
1.0 Deg
0.1 Deg
Celsius
Fahrenheit
Temperature
Raw Value
Resolution (Temp):
Output Unit (Temp):
Value Type:
For RTD / Resistance Input For TC / mV Input
1.0 Deg
0.1 Deg
Celsius
Fahrenheit
On Board
Channel 1
Resolution (Temp):
Output Unit (Temp):
Cold Junction Compensator:
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com