Hardware reference guide
Intrinsically Safe Modules
35013379 02 October 2007 425
Thermocouple/
Millivolt Map
Register
Assignments
When the 140AII33000 is configured as a Thermocouple/Millivolt input module, it
requires ten contiguous input (3x) registers assigned as follows.
Register 1 Channel 1 data
Register 2 Channel 2 data
Register 3 Channel 3 data
Register 4 Channel 4 data
Register 5 Channel 5 data
Register 6 Channel 6 data
Register 8 Channel 8 data
Register 7 Channel 7 data
Register 9 Input Status Word
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 = Range warning on Channel 8
1 = Range warning on Channel 7
1 = Range warning on Channel 6
1 = Range warning on Channel 5
1 = Range warning on Channel 4
1 = Range warning on Channel 3
1 = Range warning on Channel 2
1 = Range warning on Channel 1
1 = Broken Wire or out of range on channel 1
1 = Broken Wire or out of range on channel 2
1 = Broken Wire or out of range on channel 3
1 = Broken Wire or out of range on channel 4
1 = Broken Wire or out of range on channel 5
1 = Broken Wire or out of range on channel 6
1 = Broken Wire or out of range on channel 7
1 = Broken Wire or out of range on channel 8
Register 10 Remote Junction Temperature
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com