Hardware reference guide
Intelligent/Special Purpose
35013379 02 October 2007 409
Specifications Specifications for the 140XBE10000 Backplane Expander are below.
Words per Drop The following tables shows Words per drop.
Specifications
Number of Connected
Backplanes
2
Maximum Distance 3 meters
Backplane Requirements
Size All backplane sizes – 3, 4, 6, 10 and 16 slot.
Slots used 1
Number of Backplane Expander
modules allowed
1 per backplane
LEDs None.
Required Addressing The Backplane Expander will look like an unfilled slot in
the PLC I/O map.
Power Requirements
Power Consumption 2.5 watts
Bus Current Required 500 mA
Connector 37 pin D-type
Compatibility
Primary Backplane No restrictions
Secondary Backplane All types of Quantum I/O modules can be used in the
secondary backplane, unless otherwise noted in the I/O
documentation.
Programming Software Modsoft V 2.6 or Concept V 2.2 at a minimum
Executive Firmware 140CPUX130X - Version 2.2
140CPUX341X - Version 1.03
140CPUx341xA - Any version
140CPUx341xB - Any version
140CPU42402 - Version 2.15
140CRA93X0X - Version 1.2
Maximum words per drop
Local I/O 64 in /64 out
Remote I/O 64 in /64 out