Run LED Status The following table lists each available state of the Run LED indicator and provides
diagnostic information for that state
Indicator State Status
On (steady) Normal operation: The NOE module is ready for network
communication.
Number of flashes in sequence
one Not used
two Not used
three No Link: the network cable is not connected or is defective.
four Duplicate IP address: The module will be set to its default IP address.
five No IP address: The module is attempting to obtain an IP address from
a BOOTP server. Module is set to default IP address.
six Invalid IP configuration. (Likely cause: Default gateway is not on the
same subnet mask. Module is set to default IP address.
seven No valid executive NOE present