READ FIRST WHEN INSTALLING A PIM-485-16-TD-NXT Addendum INSTALLING , CONFIGURING & OPERATING PANEL INTERFACE MODULE RS485 NexSentry Star I/II Version (PIM-485-16-TD-NXT) The most current version of this document is available for download at: http://www.irsupport.net IR Security & Safety 575 Birch St.
575 Birch St. Forestville, Ct 06010 (866) 322-1237 (866) 322-1233 Fax World Wide Web http://www.irsupport.net Copyright © 2003-2004 Ingersoll-Rand, all rights reserved. No part of this document can be reproduced, transmitted, or transcribed in any form by electrical, mechanical, optical, manual, or otherwise without the prior written consent of Ingersoll-Rand.
INSTALLATION & OPERATING INSTRUCTIONS TABLE OF CONTENTS 1. 2. Wyreless Access™ System (WAS)......................................................................................................................4 1.1 Overview .......................................................................................................................................................4 1.2 Panel Interface Module-RS485-NexSentry (PIM-485-16-TD-NXT) ............................................................
1. Wyreless Access™ System (WAS) 1.1 Overview Every access control system that uses Wyreless AccessTM contains two different types of modules (Figure 1-1): • at least one Wyreless Panel Interface Module (WPIM), and • at least one Wyreless Access Point Module (WAPM) Figure 1-1 – Wyreless Access System Block Diagram The WPIM is wired to the access control panel and ideally is installed very close to the access control panel.
1.2 Panel Interface Module-RS485-NexSentry (PIM-485-16-TD-NXT) The Panel Interface Module-RS485-NexSentry (PIM-485-16-TD-NXT) is a product in Schlage’s Wyreless Panel Interface Module (WPIM) category. The PIM-485-16-TD-NXT is the wireless interface to a NexSentry Star I or Star II Access Control Unit (Figure 1-2). Figure 1-2 – PIM-485-16-TD-NXT Block Diagram Up to 16 (8 for a Star I) PIM-485-16-TD-NXT can be connected via a 2 wire polled, RS-485 interface to a Star I/II.
The PIM-485-16-TD-NXT can be ordered with one of three possible enclosures. The xx in the PIM-48516-TD-NXT sales model number indicates the maximum number of WAPM’s that can be controlled by that sales model. Table 1-1 & Table 1-2 shows the PIM-485-16-TD-NXT sales model and its major specifications.
MAXIMUM ACCESS CONTROL PANEL NUMBER LOCATION INTERFACE/DESCRIPTION OF WAPMs MODEL ENCLOSURE PIM-485-16-TD-NXT plastic 16 ANT-REMOTE plastic n/a ANT-6DB-FLAT plastic n/a indoor RS485 indoor outdoor indoor outdoor Optional remote omnidirectional antenna Optional remote 6db gain directional antenna Table 1-2- PIM-485-16-TD-NXT Sales Model Table IR Security & Safety P/N: M053-016-A 575 Birch St., Forestville, Connecticut 06010 / (860) 584-9158 / (860) 584-2136 fax http://www.irsupport.
2. Installing the PIM-485-16-TD-NXT 2.1 Configuring the PIM-485-16-TD-NXT to Emulate DR42xx DigiReaders The Schlage Configuration & Demonstration Tool (CDT, version 1.4 or higher) must be used to configure each PIM-485-16-TD-NXT to emulate the desired number and address of DR42xx DigiReaders. The PIM-485-16-TD-NXT must be connected to the PC running the CDT using a serial connection (either RS485 or RS232).
ADDR/READER MIRO 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 x x x x x x x x x+1 x+1 x+1 x+1 x+1 x+1 x+1 x+1 Door Position Switch 1 3 5 6 9 11 13 15 1 3 5 6 9 11 13 15 Point Numbers Request to Exit 2 4 6 8 10 12 14 16 2 4 6 8 10 12 14 16 Strike Relay 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 Table 2-2 - PIM, MIRO, Reader, Point Number Association for one PIM IR Security & Safety P/N: M053-016-A 575 Birch St., Forestville, Connecticut 06010 / (860) 584-9158 / (860) 584-2136 fax http://www.irsupport.
2.2 Connecting the PIM-485-16-TD-NXT to a Star I/II Access Control Unit Note: Make certain that that Star I/II Terminal Block TB1 is configured for the S-NET communication protocol. 2.2.1 PIM-485-16-TD-NXT using an Original PIM PCB Star I/II – TB1 SNET A SNET B PIM-485-16-TD-NXT – J6 A B Table 2-3 – RS485 Connection: Original PIM PCB & RAMM 2.2.
2.3 Linking the PIM-485-16-TD-NXT to WAPMs 2.3.1 How to Set an RF Channel One of fifteen RF channels can be set using DIP switch SW7 on the PIM.
2.4 PIM-485-16-TD-NXT Card Formats The PIM-485-16-TD-NXT accepts a 26 bit Wiegand format, strips off the two parity bits and the eight bit facility code field, the resulting 16 bit card number field is sent to the STAR I/II controller for further processing. 2.5 PIM-485-16-TD-NXT Alarms THIS FEATURE HAS NOT BEEN IMPLEMENTED YET. Each WAPM linked to a PIM-485-16-TD-NXT can report five different types of alarms: low battery, reader tamper, loss of RF communications, lock motor stall, and PIM tamper.
3. Contacting Schlage For questions regarding Wyreless Access™: customerservice@recognition-source.com sales@recognition-source.com techsupport@recognition-source.com www.recognition-source.com (630) 762-4450 (630) 762-4444 fax IR Security & Safety P/N: M053-016-A 575 Birch St., Forestville, Connecticut 06010 / (860) 584-9158 / (860) 584-2136 fax http://www.irsupport.
4. FCC Compliance & Warnings 4.1 FCC Compliance • This device has been authorized by the FCC Rules and Industry Canada. • This device complies with the limits for a Class B digital device and a Class B intentional radiator, pursuant to Part 15 of the FCC Rules and with RSS-210 of Industry Canada.
5. Revision History Version X001 X001.1 001 002 Date 07/03/02 09/06/02 09/12/02 01/13/04 Changes preliminary in house release for comments updated Configuring and Linking sections for new CDT version released for publication added Star II/PIM/CDT addressing information/rules, removed obsolete sales models, added new sales model PIM-485-16-TD-NXT, added card format section IR Security & Safety P/N: M053-016-A 575 Birch St., Forestville, Connecticut 06010 / (860) 584-9158 / (860) 584-2136 fax http://www.