Datasheet
2 EMC/EMI Products Schaffner Group Datasheets 2017
Filter selection table
Filter* Rated current Leakage current** Power loss Input/Output Weight
@ 40°C (25°C) @ 400 VAC/50 Hz @ 25 °C/ 50Hz connections
[A] [mA] [W] [kg]
FN 356-16-.. 16 (18.4) 0.43 7.0 -06 -29 1.2
FN 356-25-.. 25 (28.8) 0.43 10.1 -24 -33 1.5
FN 356-36-.. 36 (41.5) 0.43 10.9 -24 -33 1.6
FN 356-50-.. 50 (57.7) 0.43 15.8 -24 -33 2.3
FN 356-100-.. 100 (115.0) 1.33 24.0 -28 -34 5.9
FN 356-150-28 150 (172.5) 8.00 45.9 -28 8.1
* To compile a complete part number, please replace the -.. with the required I/O connection style.
** Maximum leakage under normal operating conditions, based on the assumption that all three phases and the neutral conductor are connected to the supply and the
consumer. In this case, the current will mainly return through the neutral line, not as earth leakage.
Typical filter attenuation
Per CISPR 17; A=50 Ω/50 Ω sym; B=50 Ω/50 Ω asym; C=0.1 Ω/100 Ω sym; D=100 Ω/0.1 Ω sym
16 A types
25 to 50 A types
100 A types
150 A types
Mechanical data
16 to 50 A types (-06, -24) 16 to 50 A types (-29, -33)